Conair MPA Refrigerator User Manual


 
The compressor may be located in the compressor electrical
enclosure or in the main chiller electrical enclosure, depend-
ing on the model of your chiller.
The compressor contactor should be replaced if:
You have checked the amp draw on each of the three-phase
legs and discovered a voltage imbalance greater than 10%.
You have checked the continuity and found that ohms at
the coil equal zero.
To replace the compressor contactor:
Disconnect and lockout the main power.
Open the electrical enclosure.
Turn the screw on
the front panel counterclockwise to open.
Disconnect the wires from the compressor con-
tactor contactor.
Label the wires to ensure you can
connect them correctly to the new contactor.
Remove and discard the old contactor.
Reverse this procedure to install the new con-
tactor.
Make sure the wires are connected correctly.
microKool Portable Chillers UGH004/0999
6-16 TROUBLESHOOTING
1
2
3
4
5
IMPORTANT:
Always
refer to the wiring dia-
grams that came with
your chiller to locate spe-
cific electrical compo-
nents. Illustrations in the
User Guide are intended
to be representative only.
WARNING: Electrical Shock Hazard
Only qualified service personnel who have been
trained on electrical testing and the procedures for
avoiding the hazards should diagnose or correct prob-
lems that require opening the unit with power on.
REPLACING THE
COMPRESSOR
CONTACTOR