Conair MPA Refrigerator User Manual


 
UGH004/0999 microKool Portable Chillers
INSTALLATION 3-3
The microKool chiller is easy to install, if you plan the loca-
tion and prepare the area properly.
Position the chiller as close to the process
machine as possible.
Make sure the installation area provides:
A three-phase power source supplying the correct
current for your chiller model. Check the serial tag on the
side of the electrical enclosure for the required voltage,
phase, frequency, full load amps, disconnect fuse size and
minimum wire connection size. Field wiring should be
completed by qualified personnel to the planned location
for the chiller. All electrical wiring should comply with
your region’s electrical codes.
A clean, well-ventilated environment.
The room temperature should not exceed 110° F (43° C)
with 95% non-condensing humidity and should not fall
below 55° F (12° C).
Minimum clearance for safe operation and mainte-
nance. Nothing should be placed on top of the unit while
the unit is operating. All models require a minimum clear-
ance of 5 ft. around the perimeter for servicing. Models
equipped with fans also require unrestricted outlet air flow.
A source of water for cooling on water-cooled units.
City, tower or chiller water may be used, as long as the
supply pressure is at least 25 psi and not more than 85 psi.
Install plumbing for process and cooling lines.
See the specification tables for the correct line and fitting
sizes. Larger line sizes are acceptable as long as they are
reduced at the chiller connections. Smaller line sizes are
not recommended.
PREPARING FOR
INSTALLATION
1
2
Process machine
Chiller
Alternate
locations
3