The chiller process inlets and outlets must be connected to the
plumbing that will circulate the temperature-controlled water
or fluid through the process. Cooling water inlets and outlets
are connected to the cooling water supply.
Remove the shipping pipe plug from the female
connections on the back of the chiller.
Install pipe to the rear of the chiller.
Use appropriately sized male NPT piping for the process
connections and the MPW condenser water connections.
Pipe and pipe threads must be clean and new. Clean
threads with solvent, removing all oil, grease and dirt.
Allow the threads to dry before proceeding.
Coat the pipe threads with thread sealant.
Follow the sealant manufacturer’s directions.
Connect the male pipe to the appropriate
female connection on the back of the unit
.
Connections are labeled on the chiller. Start by hand until
the threads engage, then use a pipe wrench to tighten the
connection only enough to prevent leaks.
Do not over-tighten!
CONNECTING
PROCESS AND
WATER SUPPLY
LINES
microKool Portable Chillers UGH004/0999
3-4 INSTALLATION
1
2
3
4
Tools for installation:
Pipe wrench large enough
for a 2-inch pipe
Premium quality Teflon
thread sealant
Process connections (NPT):
MPW-1.5 MPW-2 MPW-3 MPW-4 MPW-5 MPW-7.5 MPW-10
MPA-1.5 MPA-2 MPA-3 MPA-4 MPA-5 MPA-7.5 MPA-11
1 in. 1 in. 1 in. 1.5 in. 1.5 in. 1.5 in. 1.5 in.
Condenser water connections (NPT):
MPW-1.5 MPW-2 MPW-3 MPW-4 MPW-5 MPW-7.5 MPW-10
1 in. 1 in. 1 in. 1.5 in. 1.5 in. 1.5 in. 1.5 in.
NOTE: Make sure the
chiller tank is full of
process fluid before
you begin operating.
Use a glycol mixture if
operating temperatures
are below 45° F. See
F
REEZE
P
ROTECTION
R
EQUIREMENTS
.
Tank
fill port
Condenser
water in
From
Process
Condenser
water out
Condenser water
connections on
MPW models only
To
Process
Tank level
sight glass