Liebert iCOM Control—Firmware Version XP1.00.010.STD
44
Figure 44 Maintenance—Basic Settings screen, page 1 of 7
Maintenance Frequency Per Year—Sets the number of expected maintenance visits in a one year
time span.
Max Bonus—Increases the time until the next required maintenance. Service personnel should
assign a bonus when a service visit finds all components working optimally.
Max Penalty—Decreases the time until the next maintenance cycle. Service personnel should assign
a penalty when a service visit finds excessive wear on components.
Last Maintenance—Date set during the service call. It also indicates to other service personnel the
date of the last visit.
Service Engineer—Provides a label for the service representative to list either the company name
or representative’s name.
Confirm PM—Confirms that the service representative has completed the preventive maintenance
and resets the next maintenance date.
Calculated Next Maintenance—Provides a date to for the next expected maintenance based on the
last preventive maintenance performed (Confirm PM), component starts, run hours and the penalty
or bonus set in the Liebert iCOM control.
Basic Settings (page 1 of 7)
SYSTEM
PASSWORD (Actual Level 0) ????
Maintenance Frequency Per Year 1
Max Bonus 0
Max Penalty 0
Last Maintenance 08/25/2011
Service Engineer NOBODY
Confirm PM No
Calculated Next Maintenance 08/2014
S001
S002
S003
S004
S005
S006
S007
S008
S009
S010
S011
to confirm
for next/previous unit
then
to select parameter
to change parameter