XV. Typical Cooling Performance Data
Outdoor Indoor PGC24 PGC30 PGC36
Air Temp.
at
Air
Temp.
Indoor
Air Temp.
Pressure @ Unit
Gauge Fittings
Amps
Indoor
Air Temp.
Pressure @ Unit
Gauge Fittings
Amps
Indoor
Air Temp.
Pressure @ Unit
Gauge Fittings
Amps
Condenser
Inlet
(Dry Bulb)
at Evap.
Inlet
(Wet Bulb)
Difference
Be tw e en
Coil Inlet
and Outlet
Low
Side
High
Side
Total to
Unit
Difference
Be tw e en
Coil Inlet
and Outlet
Low
Side
High
Side
Total to
Unit
Difference
Be tw e en
Coil Inlet
and Outlet
Low
Side
High
Side
Total to
Unit
A B CDE B CDE B CDE
° F. ° F. ° F. PSIG PSIG Amps ° F. PSIG PSIG Amps ° F. PSIG PSIG Amps
77 7 92 325 12.8 7 89 320 15.8 7 88 351 19.3
115 72 12 91 324 12.7 12 89 322 15.9 12 87 352 19.4
67 17 91 324 12.7 17 88 322 15.8 17 87 352 19.3
62 23 90 326 12.8 23 87 322 15.8 23 86 352 19.3
77 7 91 308 12.2 7 89 304 15.2 7 87 332 18.5
110 72 12 90 304 12.1 12 88 303 15.1 12 87 332 18.5
67 17 80 304 12.1 17 88 303 15.1 17 86 331 18.4
62 23 89 304 12.1 23 87 302 15.1 23 85 329 18.4
77 7 90 288 11.7 7 88 285 14.5 7 86 311 17.6
105 72 12 90 286 11.6 12 88 285 14.5 12 86 310 17.6
67 18 89 286 11.6 18 87 283 14.5 18 85 312 17.6
62 23 88 286 11.6 23 86 282 14.4 23 84 311 17.6
77 8 89 269 11.1 8 87 267 13.9 8 86 293 16.9
100 72 12 89 269 11.1 12 87 267 13.9 12 85 293 16.9
67 18 89 271 11.2 18 86 267 13.9 18 85 292 16.8
62 23 88 271 11.2 23 85 267 13.9 23 84 290 16.7
77 8 89 255 10.7 8 87 251 13.4 8 85 275 16.2
95 72 13 88 251 10.6 13 86 249 13.3 13 85 274 16.1
67 18 88 252 10.7 18 86 249 13.3 18 84 274 16.1
62 23 87 254 10.7 23 85 249 13.3 23 83 274 16.1
77 8 88 237 10.2 8 86 234 12.9 8 84 255 15.4
90 72 13 88 236 10.2 13 86 232 12.8 13 84 255 15.4
67 18 87 234 10.2 18 86 231 12.8 18 83 256 15.4
62 24 86 235 10.2 24 84 231 12.8 24 83 254 15.4
77 8 87 222 9.8 8 86 217 12.3 8 84 240 14.8
85 72 13 87 221 9.8 13 85 217 12.4 13 83 238 14.8
67 18 86 221 9.8 18 84 216 12.3 18 83 238 14.7
62 24 86 220 9.8 24 83 216 12.3 24 82 239 14.8
77 8 87 203 9.3 8 85 202 11.9 8 83 224 14.3
80 72 13 86 203 9.3 13 84 203 12.0 13 83 223 14.2
67 18 86 205 9.4 18 84 202 11.9 18 82 221 14.2
62 24 85 206 9.4 24 83 202 11.9 24 81 221 14.2
77 8 86 189 9.0 8 84 189 11.6 8 83 208 13.7
75 72 13 86 189 9.0 13 84 189 11.6 13 82 207 13.7
67 19 85 191 9.0 19 83 189 11.6 19 82 207 13.7
62 24 85 190 9.0 24 82 187 11.6 24 81 206 13.6
A Columns - All data based on indoor dry bulb of 80° F and rated air flow. As indoor dry bulb temperature increases, a slight increase wil
l occur in indoor air temperature differential
between inlet and outlet. Low and high side pressures and power will not change.
B Columns - A properly operating unit should be within ±3° F of the typical (dry bulb) value shown.
C Columns - A properly operating unit should be within ±3 PSIG of the typical value shown.
D Columns - A properly operating unit should be within ±7 PSIG of the typical value shown.
E Columns - A properly operating unit should be within ±2 amps of the typical value shown.
Table 8A