1) Forced Start Operation Function
1-1) Forced start operation is selected if the test key is pressed once while in the test mode. At that time the buzzer
executes an alarm by making a beep sound.
2-1) If forced start operation is selected , then COMP. operates immediately without a 5 minute delay, regardless of
operating mode. If it is during defrosting, defrosting shall promptly stop.
3-1) If forced start operation is selected, then the COMP. and F FAN perform a PULL-DOWN operation for 24 hours
while the R compartment is controlled by the set temperature.
4-1) The forced start operation is performed continuously performed until completed, canceled or converted to an other
mode (forced F, R, CF, CR defrosting).
5-1) If the forced start operation is selected , then along with it, a automatic selection is made for the F compartment
”-13and for the R compartment “33.8These settings are not changed (maintains “-13and “33.8)
even if forced defrosting or test cancellation is selected after more than 1 minute elapses under the condition
where forced start operation has been selected Nevertheless the setting are restored to the temperatures that
were set before the change to ”-13and “33.8if forced defrosting or test cancellation is selected before 1
minute elapses from the time when the forced start operation was selected.
6-1) If forced start operation is finished(24 hours), then F, CF compartment defrosting is executed regardless
of previous condition.
7-1) Next, it proceeds normal defrosting opera according to CASE judgment, performing defrosting of the R
compartment defrosting.
8-1) If randomly canceled during forced start operation (by cancellation mode), the COMP. ON time period during the
forced start operation is also added to the accumulation to be considered for the defrosting period.
9-1) The power freezing and power refrigeration functions do not work during forced start operation. If any of these
functions is selected, the LED display for the selected POWER function turns off spontaneously after
approximately 10 seconds..
2) Forced Defrosting Function
1-1) If test button is pressed a second time, then R compartment / CR compartment defrosting is executed, and if the
test button is pressed a third time, then simultaneous defrosting of F, CF, R, CR compartments is executed, and a
beeping sound alarm is also executed.
2-1) The beeping sound alarm is executed until completion time of the heating and pause time.
3) Test Cancellation Mode
3-1) If the display panel is converted to the test mode and the test button is pressed once more, under the
simultaneous defrosting condition, then defrosting of freeze and refrigeration partitions is canceled simultaneously
to return to normal operation. Or if main power is turned on after turnoff, then all test functions are canceled.