U-Line CLR2060SSHR Ice Maker User Manual


 
92
Design
Features
Performance
CONNECTING A DRAIN PUMP
If a gravity drain connection is not available, U-Line strongly recommends the use of the U-Line P60 drain
pump. If your CLR2060 is not equipped with a factory installed pump, a P60 drain pump is available
through your Dealer, or direct from U-Line. If a pump other than the U-Line P60 drain pump is to be used,
it must meet the following specifications:
It must be UL listed and have a UL listed, 120 VAC, 3-wire grounded power cord.
Overall maximum outside dimensions of 8-3/4" wide x 5-3/4" deep x 7-3/4" high.
Minimum flow rate of 15 gallons per hour at 10 feet of lift.
It must have a sealed sump which does not allow water leakage in the case of a power outage, restricted
drain or pump failure.
It must have a check valve in the discharge line to prevent waste water return to the pump.
It must have an overflow protection control which will shut off power to the ice maker in the event of
a pump failure.
Operating temperature range of 50°F to 110°F (10°C to 40°C).
If your CLR2060 is not equipped with a P60 drain pump or an equivalent drain pump, severe damage and
costly repair could result in the event of a power outage, restricted drain or pump failure.
CLR2060 MODEL
Plumbing installation must observe all state and local codes. All water and drain connections
MUST BE made by a licensed/qualified plumbing contractor. Failure to follow recommendations
and instructions may result in damage and/or harm.
!