Vulcan-Hart VCG10H, VCG10F, VCG20H, ML-126836, ML-126837, ML-126838 Oven User Manual


 
– 7 –
GAS CONNECTION
All gas supply connections and any pipe joint compound must be resistant to the action of propane
gases. The machine connection is
3
/4" external thread. A manual valve (supplied) must be installed
in the gas supply line ahead of the appliance. Make sure piping is clean and free of obstructions, dirt
or pipe joint compound. Recommended gas supply pressures are 7" W.C. (Water Column) for natural
gas and 11" W.C. for propane. The gas line must be capable of delivering gas to the oven without
excessive pressure drop at the rate specified on the rating plate.
The oven is equipped with a factory preset pressure regulator. Natural gas pressure regulators are
preset for 3.5" W.C. for both ovens and steam generators. Propane gas pressure regulators for 10 level
ovens are preset for 10" W.C. for both the oven and steam generator. Propane gas pressure regulators
for 20 level half depth ovens are preset for 8" W.C. for the oven burner and 10" W.C. for the steam
generator. Gas pressure must be checked for correct operating pressure at start-up.
Caster equipped ovens must be installed with a connector that complies with the
Standard for
Connectors for Movable Gas Appliances
, ANSI-Z21.69 (latest edition) [in Canada, CAN/CGA-6.16,
latest edition] and a quick-disconnect device that complies with the
Standard for Quick-Disconnect
Devices for Use with Gas Fuel
, ANSI-Z21.41 (latest edition) [in Canada, CAN 1-6.9, latest edition]. A
gas line strain relief must be provided to limit the movement of the oven without depending on the
connector and the quick-disconnect device or its associated piping to limit oven movement. Attach the
strain relief to the rear of the oven at the location provided. If it is necessary to disconnect the restraint
during service or maintenance, first turn off the gas supply. Reconnect the restraint before returning
the oven to its original installed location and turning the gas supply on.
WARNING: PRIOR TO LIGHTING, CHECK ALL JOINTS IN THE GAS SUPPLY LINE FOR LEAKS.
USE SOAP AND WATER SOLUTION. DO NOT USE AN OPEN FLAME.
The convection burner and the steam generator burner are ignited automatically by electric igniters;
there are no pilot lights. See Start-Up Procedure, page 9.
Keep the appliance area free and clear from all combustible substances. Do not obstruct the flow of
combustion and ventilation air. Make sure there is an adequate supply of air in the room to allow for
combustion at the burners and exhaust by the vent hood system.
Testing the Gas Supply Piping System
When test pressures exceed
1
/2 psig (3.45 kPa), the oven and its individual shutoff valve must be
disconnected from the gas supply piping system.
When test pressures are
1
/2 psig (3.45 kPa) or less, the oven must be isolated from the gas supply piping
system by closing its individual shutoff valve.
GAS INPUT
Model Gas Type
Burner Input Rating Gas Pressure
Oven Steam Generator Total Convection Steam
VCG10H
Natural 67,000 BTU/Hr 40,000 BTU/Hr 107,000 BTU/Hr 3.5" W.C. 3.5" W.C.
Propane 69,000 BTU/Hr 40,000 BTU/Hr 109,000 BTU/Hr 10.0" W.C. 10.0" W.C.
VCG10F
Natural 85,000 BTU/Hr 45,000 BTU/Hr 130,000 BTU/Hr 3.5" W.C. 3.5" W.C.
Propane 85,000 BTU/Hr 45,000 BTU/Hr 130,000 BTU/Hr 10.0" W.C. 10.0" W.C.
VCG20H
Natural 70,000 BTU/Hr 58,000 BTU/Hr 128,000 BTU/Hr 3.5" W.C. 3.5" W.C.
Propane 70,000 BTU/Hr 58,000 BTU/Hr 128,000 BTU/Hr 8.0" W.C. 10.0" W.C.