York R134A Refrigerator User Manual


 
JOHNSON CONTROLS10
Temperatures and Flows
TEMPERATURE AND FLOWS
(English Units)
NOTES:
1. For leaving brine temperature below 40°F (4.4°C), contact your nearest Johnson Controls ofce for application requirements.
2. For leaving water temperature higher than 60°F (15.6°C), contact the nearest Johnson Controls ofce for application guidelines.
3. The evaporator is protected against freezing to -20°F (-28.8°C) with an electric heater as standard.
MODEL
NUMBER
YCIV
LEAVING WATER
TEMPERATURE (°F)
COOLER
3
FLOW
(GPM)
AIR ON CONDENSER (°F)
MIN.
1
MAX.
2
MIN. MAX. MIN. MAX
50 Hz 60 Hz
0600(S/P) 0157(S/P) 40 60 140 675 0 125
0590(E/V) 0157(E/V) 40 60 160 750 0 125
0650(S/P) 0177(S/P) 40 60 160 750 0 125
0630(E/V) 0177(E/V) 40 60 160 750 0 125
0720(S/P/) 0187(S/P) 40 60 160 750 0 125
0700(E/V) 0187(E/V) 40 60 160 750 0 125
0760(E/V) 0197(E/V) 40 60 180 750 0 125
0770(S/P) 0207(S/P) 40 60 180 800 0 125
0800(E/V) 0207(E/V) 40 60 180 750 0 125
0840(S/P) 0227(S/P) 40 60 180 800 0 125
0830(E/V) 0227(E/V) 40 60 180 750 0 125
0920(S/P) 0247(S/P) 40 60 180 800 0 125
0930(E/V) 0247(E/V) 40 60 180 800 0 125
1000(S/P) 0267(S/P) 40 60 180 800 0 125
1050(E/V) 0267(E/V) 40 60 250 1200 0 125
1070(S/P) 0287(S/P) 40 60 250 1200 0 125
1120(E/V) 0287(E/V) 40 60 250 1200 0 125
1180(S/P) 0307(S/P) 40 60 300 1200 0 125
1220(E/V) 0327(E/V) 40 60 300 1200 0 125
1340(S/P) 0357(S/P) 40 60 300 1200 0 125
1380(E/V) 0357(E/V) 40 60 300 1200 0 125
1500(S/P) 0397(S/P) 40 60 300 1200 0 125