York R134A Refrigerator User Manual


 
JOHNSON CONTROLS88
Dimensions – SI - continued
Notes:
1. Placement on a level surface free of obstructions (including snow, for winter operation) or air recirculation ensures rated performance,
reliable operation, and ease of maintenance. Site restrictions may compromise minimum clearances indicated below, resulting in unpre-
dictable air patters and possible diminished performance. Johnson Controls’ unit controls will optimize the operation without nuisance
high pressure safety cutouts; however, the system designer MUST consider potential performance degradation.
Access to the unit control center stipulates the unit is no higher than on spring isolators. Recommended minimum clearances: side to wall
- 2m; rear to wall - 2m; control panel end to wall - 1.2m; top - no obstructions whatsoever; distance between adjacent units - 10’. No more
than one adjacent wall may be higher than the unit.
YCIV A B C D
0760E/V
518 714 2174 2852
0770S/P
564 660 2009 2878
0890S/P
564 660 2009 2878
VIEW C-C
VIEW B-B
305
CONTROL ENTRY
76 WIDE X 343 HIGH
38
102
POWER ENTRY
254 WIDE X 330 HIGH
44
POWER ENTRY IS ON BOTTOM OF PANEL
2238
B
(EDGE OF UNIT
TO COOLER
CONNECTION)
A
C
B
B
VIEW A-A
C
YCIV0760E/V, YCIV0770S/P, and YCIV0890S/P