York R134A Refrigerator User Manual


 
JOHNSON CONTROLS8
Accessories and Options (Continued)
BUILDING AUTOMATION SYSTEM INTERFACE:
Chiller to accept 4 to 20mA or 0 to 10 VDC input to
reset the leaving chilled liquid temperature. (Factory
Mounted)
MULTI-UNIT SEQUENCE CONTROL:
Separate sequencing control center provided to permit
control of up to eight chillers in parallel based of mixed
liquid temperature (interconnecting wiring by others).
(Field Mounted)
VIBRATION ISOLATION:
Neoprene Isolation – Recommended for normal in-
stallations. Provides very good performance in most
applications for the least cost. (Field mounted)
1” Spring Isolators – Level adjustable, spring and
cage type isolators for mounting under the unit base
rails. 1” nominal deection may vary slightly by appli-
cation. (Field mounted)
2” Seismic Spring Isolators – Restrained Spring-Flex
Mountings incorporate a rugged welded steel hous-
ing with vertical and horizontal limit stops. Housings
designed to withstand a minimum 1.0g accelerated
force in all directions to 2” (51mm). Level adjustable,
deection may vary slightly by application. (Field
mounted)
BUY AMERICAN ACT COMPLIANCE - In keeping with
the “Buy America Act”, products will be comprised of 50%
or more U.S. content and manufactured (nal assembly)
in the U.S.A.
SERVICE ISOLATION VALVE – Service suction isola-
tion added to unit for each refrigerant circuit. (Factory
Mounted)
CHICAGO CODE RELIEF VALVE - Special relief valves
per Chicago code. (Factory Mounted)
PRESSURE RELIEF (CE/PED) SERVICE VALVE KIT
- Each relief valve is mounted on a sealable ball valve to
aid maintenance. (Factory Mounted)
cooler, etc.), yet provides free air ow. This can cut
installation cost by eliminating the need for separate,
expensive fencing. (Factory mounted)
Louvered Panels (condenser coils only) – Painted
steel to match unit panels, louvered panels are
mounted over the exterior condenser coil faces on the
sides of the unit to visually screen and protect coils.
(Factory mounted)
Louvered Panels (full unit) – Painted steel to match
unit panels, to protect condenser coils from incidental
damage, visually screen internal components, and
prevent unauthorized access to internal components.
(Factory mounted)
Louvered (Condensers)/Wire Panels (Mechanical)
– Louvered steel panels on external condenser coil
faces, painted to match unit panels. Heavy gauge,
welded wire-mesh, coated to resist corrosion, around
base of machine to restrict unauthorized access. (Fac-
tory Mounted)
EVAPORATOR OPTIONS:
1-1/2” Insulation – Double thickness insulation pro-
vided. (Factory Mounted)
Raised Face Flange Accessory for cooler nozzles:
150 PSIG (10.3 bar), welded anges (eld kit,
matching pipe ange by contractor).
150 PSIG (10.3 bar) companion weld anges. (eld
kit - Not available with 460V units).
150 PSIG (10.3 bar), ANSI/AWWA C-606 COU-
PLINGS (eld kit, matching pipe ange by contrac-
tor).
Opposite Handed evaporator water connections
for ease of installation. Standard water connections
are on the left-hand side of the unit, when viewed from
the control panel end.
FLOW SWITCH ACCESSORY : Vapor proof SPDT, NEMA
3R switch, 150 PSIG (10.3 bar) DWP, 20°F to 250°F
(-28.9°C to 121.1°C) with 1” NPT (IPS) connection for
upright mounting in horizontal pipe (This ow switch or
equivalent must be furnished with each unit). (Field
Mounted).
DIFFERENTIAL PRESSURE SWITCH - Alternative to the
paddle-type ow switch. 3-45 PSIG (0.2-3 bar) range with
1/4" NPTE pressure connections. (Field Mounted)