TEMPERATURE AND FLOWS
(SI Units)
NOTES:
1. For leaving brine temperature below 4.4°C, contact your nearest Johnson Controls ofce for application requirements.
2. For leaving water temperature higher than 15.6°C, contact the nearest Johnson Controls ofce for application guidelines.
3. The evaporator is protected against freezing to -28.8°C with an electric heater as standard.
MODEL
NUMBER
YCIV
LEAVING WATER
TEMPERATURE (°C)
COOLER
3
FLOW
(l/s)
AIR ON CONDENSER (°C)
MIN.
1
MAX.
2
MIN. MAX. MIN. MAX
50 Hz 60 Hz
0600(S/P) 0157(S/P) 4.4 15.6 8.8 42.6 -17.8 51.7
0590(E/V) 0157(E/V) 4.4 15.6 10.1 47.3 -17.8 51.7
0650(S/P) 0177(S/P) 4.4 15.6 10.1 47.3 -17.8 51.7
0630(E/V) 0177(E/V) 4.4 15.6 10.1 47.3 -17.8 51.7
0720(S/P/) 0187(S/P) 4.4 15.6 10.1 47.3 -17.8 51.7
0700(E/V) 0187(E/V) 4.4 15.6 10.1 47.3 -17.8 51.7
0760(E/V) 0197(E/V) 4.4 15.6 11.4 47.3 -17.8 51.7
0770(S/P) 0207(S/P) 4.4 15.6 11.4 50.5 -17.8 51.7
0800(E/V) 0207(E/V) 4.4 15.6 11.4 47.3 -17.8 51.7
0840(S/P) 0227(S/P) 4.4 15.6 11.4 50.5 -17.8 51.7
0830(E/V) 0227(E/V) 4.4 15.6 11.4 47.3 -17.8 51.7
0920(S/P) 0247(S/P) 4.4 15.6 11.4 50.5 -17.8 51.7
0930(E/V) 0247(E/V) 4.4 15.6 10.1 47.3 -17.8 51.7
1000(S/P) 0267(S/P) 4.4 15.6 11.4 50.5 -17.8 51.7
1050(E/V) 0267(E/V) 4.4 15.6 11.4 50.5 -17.8 51.7
1070(S/P) 0287(S/P) 4.4 15.6 15.8 75.7 -17.8 51.7
1120(E/V) 0287(E/V) 4.4 15.6 15.8 75.7 -17.8 51.7
1180(S/P) 0307(S/P) 4.4 15.6 18.9 75.7 -17.8 51.7
1220(E/V) 0327(E/V) 4.4 15.6 18.9 75.7 -17.8 51.7
1340(S/P) 0357(S/P) 4.4 15.6 18.9 75.7 -17.8 51.7
1380(E/V) 0357(E/V) 4.4 15.6 18.9 75.7 -17.8 51.7
1500(S/P) 0397(S/P) 4.4 15.6 18.9 75.7 -17.8 51.7