York R134A Refrigerator User Manual


 
JOHNSON CONTROLS
FORM 201.23-EG1 (1007)
57
Contact your nearest Johnson Controls Sales Ofce for weight data.
Refrigerant R-134a
STANDARD EFFICIENCY
MODEL NUMBER (YCIV____ S/P)
General Unit Data
60Hz 0287 0307 0357 0397
50Hz 1070 1180 1340 1500
Number of Independent Refrigerant Circuits 3 3 3 3
Refrigerant Charge, R-134a, Ckt.-1/Ckt.-2, lbs 185/170/170 185/185/170 185/185/230 230/230/230
Oil Charge, Ckt.-1/Ckt.-2, gal. 5/4/4 5/4/4 5/5/5 5/5/5
Glycol Charge (43% concentration), gal 5.4 5.5 6.0 6.3
Comp.s, Semihermetic Screw
Quantity per Chiller 3 3 3 3
Condensers, High Efciency Fin/Tube with Integral Subcooler
Total Chiller Coil Face Area, ft2 381 411 469 528
Number of Rows 3 3 3 3
Fins per Inch 17 17 17 17
Condenser Fans
Number, Ckt.-1/Ckt.-2 5/4/4 5/4/4 5/5/6 6/6/6
Low Noise Fans
Fan Motor, HP/kWi 2/1.8 2/1.8 2/1.8 2/1.8
Total Chiller Airow, cfm 169000 182000 208000 234000
Ultra Quiet Fans
Fan Motor, HP/kWi 2/1.50 2/1.50 2/1.50 2/1.50
Total Chiller Airow, cfm 169000 182000 208000 234000
Dual Speed Fans - Normal Speed
Fan Motor, hp 2 2 2 2
Total Chiller, CFM 143000 143000 165000 165000
Dual Speed Fans - Lower Speed
Fan Motor, hp 2 2 2 2
Total Chiller, CFM 109200 109200 126000 126000
High Static Fans
Fan Motor, hp 5 5 5 5
Total Chiller, CFM 169000 182000 208000 234000
Evaporator, Direct Expansion
Water Volume, gals. 202.0 236.0 236.0 236.0
Maximum Water Side Pressure, PSIG 150 150 150 150
Maximum Refrigerant Side Pressure, PSIG 235 235 235 235
Minimum Chilled Water Flow Rate, gpm 250 300 300 300
Maximum Chilled Water Flow Rate, gpm 1200 1200 1200 1200
Water Connections, inches 10 10 10 10