Standard Efciency Ratings – SI - 380V/60Hz
MODEL: YCIV0157S/P
AIR TEMPERATURE ON - CONDENSER (°C)
LCWT 25.0 30.0 35.0 40.0 45.0 46.0
(°C) KWi KWi COP KWi KWi COP KWi KWi COP KWi KWi COP KWi KWi COP KWi KWi COP
5.0
528.8 133.1 3.6 520.9 152.2 3.2 511.8 172.8 2.8 497.4 196.1 2.4 462.2 214.6 2.0 455.0 218.5 2.0
6.0
543.2 134.0 3.7 535.0 152.9 3.2 525.5 173.7 2.8 509.5 196.7 2.4 473.3 215.3 2.1 465.8 219.2 2.0
7.0
557.9 134.9 3.8 549.4 153.8 3.3 539.5 174.5 2.9 521.7 197.3 2.5 484.5 216.0 2.1 476.8 219.9 2.0
8.0
572.9 135.8 3.8 564.1 154.6 3.4 553.7 175.4 2.9 533.9 197.9 2.5 495.5 216.9 2.2 487.9 220.6 2.1
9.0
588.0 136.8 3.9 578.9 155.6 3.4 568.2 176.3 3.0 546.3 198.5 2.6 507.2 217.5 2.2 499.2 221.3 2.1
10.0
603.4 137.9 4.0 594.1 156.6 3.5 583.0 177.3 3.1 558.9 199.1 2.6 519.0 218.1 2.2 510.8 222.0 2.2
11.0
619.1 139.1 4.1 609.5 157.6 3.6 598.0 178.4 3.1 571.6 199.7 2.7 531.0 218.7 2.3 522.6 222.6 2.2
12.0
635.0 140.3 4.1 625.1 158.7 3.6 613.2 179.4 3.2 584.5 200.3 2.7 542.9 219.3 2.3 532.1 221.1 2.3
13.0
651.2 141.6 4.2 641.0 159.8 3.7 628.7 180.5 3.2 597.5 201.0 2.8 555.1 219.9 2.4 537.5 215.9 2.3
MODEL: YCIV0177S/P
AIR TEMPERATURE ON - CONDENSER (°C)
LCWT 25.0 30.0 35.0 40.0 45.0 46.0
(°C) KWi KWi COP KWi KWi COP KWi KWi COP KWi KWi COP KWi KWi COP KWi KWi COP
5.0
587.3 146.6 3.7 576.4 167.9 3.2 563.2 190.9 2.8 536.0 208.9 2.4 491.4 218.9 2.1 462.3 206.9 2.1
6.0
603.7 147.6 3.8 592.6 168.9 3.3 579.1 192.0 2.8 550.1 209.5 2.5 496.5 214.8 2.2 467.9 203.3 2.2
7.0
620.4 148.6 3.8 609.2 169.9 3.3 595.2 193.1 2.9 563.9 210.0 2.5 502.4 210.9 2.2 474.0 199.7 2.2
8.0
637.4 149.7 3.9 626.0 170.9 3.4 611.2 193.9 3.0 577.7 210.4 2.6 508.8 207.2 2.3 479.4 195.7 2.3
9.0
654.7 150.8 4.0 643.0 171.9 3.5 626.8 194.3 3.0 591.8 210.7 2.6 514.8 203.2 2.4 484.4 191.6 2.4
10.0
672.0 152.0 4.1 660.4 173.1 3.5 642.6 194.8 3.1 605.9 211.0 2.7 520.5 199.0 2.5 488.9 187.6 2.4
11.0
689.4 153.4 4.1 677.8 174.4 3.6 658.6 195.3 3.2 620.3 211.4 2.8 525.7 194.9 2.5 493.2 183.6 2.5
12.0
707.1 154.9 4.2 695.4 175.6 3.7 674.7 195.8 3.2 634.8 211.7 2.8 530.6 190.8 2.6 497.4 179.6 2.6
13.0
725.1 156.4 4.3 713.3 177.0 3.7 691.0 196.4 3.3 649.5 212.0 2.9 534.7 186.7 2.7 501.5 175.7 2.7
MODEL: YCIV0187S/P
AIR TEMPERATURE ON - CONDENSER (°C)
LCWT 25.0 30.0 35.0 40.0 45.0 46.0
(°C) KWi KWi COP KWi KWi COP KWi KWi COP KWi KWi COP KWi KWi COP KWi KWi COP
5.0
639.4 158.1 3.7 628.8 180.6 3.2 616.7 205.2 2.8 594.6 230.0 2.4 551.9 245.6 2.1 543.3 248.7 2.1
6.0
657.2 159.2 3.8 646.3 181.6 3.3 633.7 206.2 2.9 608.9 230.4 2.5 564.8 246.2 2.2 556.2 249.2 2.1
7.0
675.3 160.5 3.9 664.0 182.7 3.4 651.0 207.3 2.9 623.5 230.8 2.5 578.2 246.7 2.2 569.2 249.7 2.2
8.0
693.7 161.8 3.9 682.0 183.9 3.4 668.4 208.5 3.0 638.4 231.1 2.6 591.9 247.1 2.3 582.6 250.2 2.2
9.0
712.5 163.2 4.0 700.4 185.1 3.5 686.2 209.8 3.1 653.5 231.5 2.7 605.8 247.4 2.3 596.2 250.6 2.2
10.0
731.6 164.7 4.1 719.0 186.5 3.6 704.3 211.0 3.1 668.7 231.8 2.7 619.9 247.8 2.4 605.6 247.6 2.3
11.0
751.0 166.3 4.1 738.0 187.9 3.6 722.8 212.3 3.2 683.9 232.2 2.8 634.3 248.1 2.4 610.8 241.4 2.4
12.0
770.7 168.0 4.2 757.3 189.4 3.7 741.6 213.7 3.2 699.5 232.6 2.8 648.9 248.4 2.5 616.4 235.6 2.5
13.0
790.7 169.9 4.3 776.9 191.0 3.8 760.7 215.3 3.3 715.3 233.0 2.9 660.2 246.2 2.5 621.8 229.7 2.5
NOTES:
1. kWo = Unit kW Cooling Capacity Output
2. kW
i
= Compressor kW Input
3. COP = Coefcient of Performance (includes condenser fan power)
4. LCWT = Leaving Chilled Water Temperature
5. Ratings based on 0.168 l/s cooler water per ton, and 0.018 (m
2