Ensure that the screws used to attach the slides to the unit do
ore than 6mm into the sides of the unit.
power supply series is designed to fit in a standard 19” equipment rack.
3.4.1 To install the Power Supply in a rack:
mount brackets to install the power supply in the rack.
Use a support bar to provide adequate support for the rear of the power supply. Do not o
struct the air exhaust at the rear panel of the unit.
3.4.2 Rack Mount Slides (optional
Use rack mount slides: General Devices P/N: CC3001
S160 or equivalent to install the unit in a
dard 19” equipment rack. Refer to Fig. 3
1 for slides assembly instructions. Use three #10
32x0.38”(max.) screws at each side. To prevent internal
age, use the specified screw length only.
3.4.3 Plastic Supporting legs
Use the four plastic legs supplied with the unit, when the power supply is mounted on a surface or
when units are stacked without rack support. When using the plastic l
egs, maximum three units can
3.5 LOCATION, MOUNTING AND COOLING
This power supply is fan cooled. The air intake is at the front panel and the exhaust is at the rear
panel. Upon installation, allow cooling air to reach the front panel ventilatio
n inlets. Allow a minimum
stricted air space at the front and the rear of the unit.
The power supply should be used in an area that the ambient temperature does not exceed +50
3.6 AC SOURCE REQUIREMENTS
ned for use in TN, TT and IT power distribution systems.
input option, the Genesys
W series can be operated from a nominal 190V to 240V. three
rent required for each model is specified in Chapter 2. Ensure that under heavy load, the AC voltage
supplied to the power supply does not fall below the specifications d