Display Voltage and Current data. Data will be returned as a string of ASCII
characters. A comma will separate the different fields. The fields, in order, are:
Measured Voltage, Programmed Voltage, Measured Current, Programmed Cu
Voltage Set Point and Under Voltage Set Point.
Example: 5.9999,6.0000,010.02,010.00,7.500,0.000
Set the low pass filter frequency of the A to D Converter for Voltage and Current
Measurement where nn = 18, 23 or 46.
D Converter filter frequency: 18,23 or 46 Hz.
Turns the output to ON or OFF. Recover from Safe
Returns the output On/Off status string.
Sets the Foldback protection to ON or OFF.
Arms the Foldback protection
Cancels the Foldback protection.
When the Foldback protection has been activated, OUT 1 command will release
arm it, while FLD 0 will cancel the protection.
Returns the Foldback protection status string:
Add (nn x 0.1) seconds to the Fold Back Delay. This delay is
standard delay. The range of nn is 0 to 255. The value is stored in eprom at AC
power down and recovered at AC power up.
Supply returns the value of the added Fold Back Delay.
Reset the added Fold Back Delay to zero.
Sets the OVP level. The OVP setting range is given in Table 7
characters after OVP is up to 12. The minimum setting level is approximately
105% of the Output Voltage setting, or the value in Table 7
aximum OVP setting level is shown in Table 5
program the OVP below this level will result in an execution error response
(“E04”). The OVP setting stays u
Returns the setting “n” where “n” is the exact string in the user’s
cal mode, returns the last setting from the front panel in a 4 digit string.
Sets OVP level to the maximum level. Refer to Table 7
Sets Under Voltage Limit. Value of “n” may be equal to PV setting, but returns
if higher. Refer to Table 7
8 for UVL programming range.
Returns the setting “n” where “n” is the exact string in the user’s “UVL n”. When
in Local mode, returns the last setting from the front panel in a 4 digit string.
estart mode to ON or OFF.
AST 1 (or AST ON): Auto restart On.
AST 0 (or AST OFF): Auto restart Off.
Saves present settings. The settings are the same as power
re erased when the supply power is switched Off and the new
“last settings” are saved.
Recalls last settings. Settings are from the last power