Fig.5-1: Series connection, local sensing
Fig.5-2: Series connection, remote sensing
5.14.1 Series connection for increased output voltage
In this mode, two units are connected so that their outputs are summed. Set the Current of each
to the maximum that the load can handle without damage. It is recommended that d
odes be connected in parallel with each unit output to prevent reverse voltage during start up s
quence or in case one unit shuts down. Each diode should be rated to at least
Output Voltage and Output Current. Refer to Fig.5
2 for series operation with local and r
Remote programming in series operation for increased output voltage:
1. Programming by external voltage:
The analog programming circuits of this power supply
are referenced to the negative output potential. Ther
fore, the circuits used to control each series connected
rated and floated from each other.
Using the SO function and PS_OK signa
Off and PS_OK circuits are refe
isolated interface common, IF_COM (J1
IF_COM terminals of different units can be co
obtain a single control circuit for the power supplies co
Do not connected power supplies from diffe
manufacturers in series or in parallel.
When power supplies are connected in s
the load or one of the output terminals is grounded,
no point may be at a greater potential of +/
from ground for models up to 60VDC Rated Output
600VDC from ground for models >60VDC
Rated Output. When using RS232/RS485 or IEEE,
er to the OUTPUT TERMINALS GROUNDING
warning in Section 3.9.11.