Chapter 4 Parameter Settings|DD Series
4-5
Paramete
r
Explanation Settings
Factory
Setting
VF
VFP
SVC
FOC
FOC
01.22
Slip Compensation Time
Constant
0.001~10.000sec 0.100 ○
01.23
Torque Compensation Gain
00~10
0 ○ ○
01.24
Slip Compensation Gain
0.00~10.00
0.00 ○ ○ ○
01.25
Slip Deviation Level
00~1000% (0:Disable) 0 ○ ○ ○
01.26
Detection Time of Slip
Deviation
0.0~10.0sec 1.0 ○ ○ ○
01.27
Over Slip Treatment
0: Warn and keep operation
1: Warn and ramp to stop
2: Warn and coast to stop
0 ○ ○ ○
01.28
Hunting Gain
00~10000 (0:Disable) 2000 ○ ○ ○
01.29
Accumulative Motor
Operation Time (Min.)
0~1439 0 ○ ○ ○ ○
01.30
Accumulative Motor
Operation Time (day)
0~65535 0 ○ ○ ○ ○
01.31
Maximum Output
Frequency
10.00~120.00Hz 50 ○ ○ ○ ○ ○
01.32
Output Frequency 1
(Base frequency /Motor
rated frequency)
0.00~120.00Hz 50 ○ ○ ○ ○ ○
01.33
Output Voltage 1(Base
voltage/Motor rated
voltage)
0.0V~240.0V 220.0 ○ ○ ○ ○ ○
01.34
Output Frequency 2
0.00~120.00Hz 0.50 ○ ○
01.35
Output Voltage 2
0.0V~240.0V 5.0 ○ ○
01.36
Output Frequency 3
0.00~120.00Hz 0.50 ○ ○
01.37
Output Voltage 3
0.0V~240.0V 5.0 ○ ○
01.38
Output Frequency 4
0.00~120.00Hz 0.00 ○ ○ ○ ○
01.39
Output Voltage 4
0.0V~240.0V 0.0 ○ ○