3Com VFD-D D Refrigerator User Manual


 
Chapter 4 Parameter Settings|DD Series
4-48
Door Close
Holding Speed
Open Door (REV)
Door Open Limit
0.0%
100.0%
Close Door (FWD)
04.00
Door Open
Speed
by Initial
04.08
Door Open
Acceleration
Time 1
04.09
Door Open
Deceleration
Time 1
04.03
Door Open High Speed 1
04.05
Door Open
Final Speed
04.01
Door Open Distance
by Initial Speed
04.04
Door Open
Final Speedby
Begins
04.06
Door Open
by Holding
Speed Begins
04.07
Door Open
Holding Speed
05.03
Door Close
High Speed 1
Door Close
Acceleration Time 1
05.05
05.04
05.06
by
Door Close
Holding
Speed
Begins
05.07
05.09
05.01
Door Close
Distance by
Initial Speed
05.00
Door Close
Initial Speed
Door Close Limit
Door Close
Final Speed
Door Close
Final Speed
Door Close
by Final Speed
Begins
05.08
Door Open Holding Torque
Control mode
VF
VFPG SVC FOCPG FOCPM
Factory setting: 20.0
Settings 0.0~100.0% (AC drive’s rated current)
Response Time of Door Open Holding Torque
Control mode
VF
VFPG SVC FOCPG FOCPM
Factory setting: 0.20
Settings 0.01~10.00sec
When the door is in the open complete position, it needs holding torque to keep the door still in complete
position. To prevent motor overload, holding torque should be set within a limit.
Door Open High Speed 2
Control mode
VF
VFPG SVC FOCPG FOCPM
Factory setting: 30.00
Settings 0.00~400.0Hz
Door Open Acceleration Time 2
Control mode
VF
VFPG SVC FOCPG FOCPM
Factory setting: 1.0
Settings 0.1~3600sec
Door Open Deceleration Time 2
Control mode
VF
VFPG SVC FOCPG FOCPM
Factory setting: 1.0
Settings 0.1~3600sec
Door Open Holding Torque 2
Control mode
VF
VFPG SVC FOCPG FOCPM
Factory setting: 0.0
Settings 0.0~150.0% (AC drive’s rated current)
Door Open Time-out Setting
Control mode
VF
VFPG SVC FOCPG FOCPM
Factory setting: 0.0
Settings 0.0~180.0sec (0.0 sec: Disable)
Holding Time for OD (Open Door)Terminal
Control mode
VF
VFPG SVC FOCPG FOCPM
Factory setting: 0.0
Settings 0.0~999.9sec (999.9 sec for always holding)
This parameter is used to clear the OD terminal signal (door open signal) when door open complete.
During the holding period, AC Motor Drive will still be in RUN status. After holding time, AC Motor Drive
will STOP. The holding time is valid only when door open has reached the complete position.