Hearth and Home Technologies VRT-GR-B-CE Range User Manual


 
19Heat & Glo • VRTIKL-CE • 7031-292 Rev E • 12/07
FLASHING
SUPPORT
BOX
STORM COLLAR
VERTICAL
TERMINATION CAP
PIPE LENGTH
FIRESTOP
11.8M
MAXIMUM
On vertical terminations use only Part #SLK-991DA
Figure 5.20
Step 1.
Check the installation instructions for required 2.5 cm clear-
ances (air space) to combustibles when passing through
ceilings, walls, roofs, enclosures, attic rafters, or other
nearby combustible surfaces. (See Figure 5.14). Check the
instructions for maximum vertical rise of the flueing system,
and any maximum horizontal offset limitations. All offsets
must fall within the set parameters of the flue charts (Figure
5.2) located on pages 11-15.
NOTE: Maximum vertical rise allowable is 11.8 M, Figure
5.2.
CONNECTED TO
WALL STRAP
WALL
STRAP
TWO 45 DEGREE
ELBOWS
METAL STRAP
Step 2.
Set the gas gas stove in its desired location. Drop a plumb
bob down from the ceiling to the position of the gas stove
flue exit, and mark the location where the flue will penetrate
the ceiling. Drill a small hole at this point. Next, drop a plumb
bob from the roof to the hole previously drilled in the ceiling,
and mark the spot where the flue will penetrate the roof.
Determine if ceiling joists, roof rafters, or other framing will
obstruct the flueing system. You may wish to relocate the
gas stove, or to offset, as shown in Figure 5.21 to avoid
cutting load bearing members.
G. Vertical Termination
1. Balance Flue Pipe
Figure 5.21
Fire Risk.
Explosion Risk.
Maintain ue clearance to combustibles as speci-
ed.
WARNING
Do not pack air space with insulation or other
materials.
Failure to keep insulation or other materials away
from ue pipe may cause re.
Figure 5.19