Trane ctv-prc007-en Refrigerator User Manual


 
41
CTV-PRC007-EN
Physical
Dimensions
CENTRAVAC WATER CONNECTION PIPE SIZE
Water Shell Size
Passes 032 050 080 142 210
EVAPORATOR Nominal Pipe Size (Inches)
1 PASS 8 10 12 16 16
2 PASS 6 8 10 12 14
3 PASS 5 6 8 10 12
CONDENSER 2 PASS 6 8 10 12 14
ENGLISH UNITS
Envelope Clearance Unit Dimensions
W/O Unit With Unit W/O Unit With Unit
Shell Mounted Mounted Tube Mounted Mounted
Shell Arrange- Starters Starters Pull Starters Starters
COMP Size ment EL EW EW CL1 CL2 Length Height Width Width
190-270 320 SS 26' 5 10' 6
1
/4 11' 4
1
/2 11' 9 3' 5 11' 3 7' 9
3
/4 5 9
1
/4 6' 7
1
/2
190-270 320 SL & LL 33' 11
1
/4 10' 6
1
/4 11' 4
1
/2 15' 6 3' 5 15' 0
1
/4 7' 9
3
/4 5 9
1
/4 6' 7
1
/2
190-270 500 SS 26' 6
3
/8 11' 4
5
/8 12' 6
7
/8 11' 9 3' 6
3
/8 11' 3 8' 2
1
/4 6' 7
5
/8 7' 9
7
/8
C 190-270 500 SL & LL 34' 0
5
/8 11' 4
5
/8 12' 6
7
/8 15' 6 3' 6
3
/8 15' 0
1
/4 8' 2
1
/4 6' 7
5
/8 7' 9
7
/8
V 300-420 500 SS 26' 6
3
/8 11' 4
5
/8 12' 5
1
/2 11' 9 3' 6
3
/8 11' 3 8' 2
1
/2 6' 7
5
/8 7' 8
1
/2
H 300-420 500 SL & LL 34' 0
5
/8 11' 4
5
/8 12' 5
1
/2 15' 6 3' 6
3
/8 15' 0
1
/4 8' 2
1
/2 6' 7
5
/8 7' 8
1
/2
E 300-420 800 SS 27' 4
1
/4 12' 5
1
/4 13' 4
5
/8 11' 9 4' 4
1
/4 11' 3 9' 6
3
/8 7' 11
1
/4 8' 7
5
/8
300-420 800 SL & LL 34' 10
1
/2 12' 5
1
/4 13' 4
5
/8 15' 6 4' 4
1
/4 15' 0
1
/4 9' 6
3
/8 7' 11
1
/4 8' 7
5
/8
480-565 500 SS 26' 6
3
/8 11' 4
5
/8 12' 5
3
/4 11' 9 3' 6
3
/8 11' 3 8' 7
1
/4 6' 7
5
/8 7' 8
3
/4
480-565 500 SL & LL 34' 0
5
/8 11' 4
5
/8 12' 5
3
/4 15' 6 3' 6
3
/8 15' 0
1
/4 8' 7
1
/4 6' 7
5
/8 7' 8
3
/4
480-565 800 SS 27' 4
1
/4 12' 5
1
/4 13' 4
5
/8 11' 9 4' 4
1
/4 11' 3 9' 8 7' 11
1
/4 8' 7
5
/8
C 480-565 800 SL & LL 34' 10
1
/2 12' 5
1
/4 13' 4
5
/8 15' 6 4 4
1
/4 15' 0
1
/4 9' 8 7' 11
1
/4 8' 7
5
/8
V 670-780 800 SS 27' 4
1
/4 12' 10 13' 10
3
/4 11' 9 4' 4
1
/4 11' 3 9' 6
3
/4 8' 4 9' 1
3
/4
H 670-780 800 SL & LL 34' 10
1
/2 12' 10 13' 10
3
/4 15' 6 4' 4
1
/4 15' 0
1
/4 9' 6
3
/4 8' 4 9' 1
3
/4
G 670-780 1420 ML & LL 35' 5
1
/4 14' 5
3
/4 15' 0
7
/8 15' 6 4' 11 15' 0
1
/4 10' 1
1
/8 9' 11
3
/4 10' 3
7
/8
920-1067 1420 ML & LL 35' 5
1
/4 14' 5
3
/4 15' 0
7
/8 15' 6 4' 11 15' 0
1
/4 10' 1
1
/8 9' 11
3
/4 10' 3
7
/8
920-1067 2100 LL 35' 5
1
/4 15 3
3
/4 15' 7 15' 6 4' 11 15' 0
1
/4 11' 0
7
/8 10' 9
3
/4 10' 10
CL1 CAN BE AT EITHER END OF MACHINE AND IS REQUIRED FOR TUBE PULL CLEARANCE.
CL2 IS ALWAYS AT THE OPPOSITE END OF MACHINE FROM CL1 AND IS REQUIRED FOR SERVICE CLEARANCE.
50 Hz Compressors
(English Units)