Trane CVHE-SVU01E-ENX39640712050 Water Dispenser User Manual


 
29
CVHE-SVU01E-EN
Operator
Interface
DynaView
(DV) is the operator
interface of the Tracer CH530 control
system utilized on the CTV machine.
The DynaView
enclosure is 9.75"
wide, 8” high and 1.6” deep. The
DynaView
display is approximately
4” wide by 3” high. Features of the
display include a touch screen and
long life LED backlight. This device is
capable of operating in 0 - 95 percent
relative humidity (non-condensing),
and is designed and tested with UV
considerations consistent with an
outdoor application in direct
sunlight. The enclosure includes a
weather tight connection means for
the RS232 service tool connection.
Touch screen key functions are
determined completely in the
software and change depending
upon the subject matter currently
being displayed. The user operates
the touch sensitive buttons by
touching the button of choice. The
selected button is darkened to
indicate it is the selected choice. The
advantage of touch sensitive buttons
is that the full range of possible
choices as well as the current choice
is always in view.
Spin values (up or down) are a
graphical user interface model used
to allow a continuously variable
setpoint, such as leaving water
setpoint to be changed. The value
changes by touching the increment
or decrement arrows.
Action buttons are buttons that
appear temporarily and provide the
operator with a choice such as Enter
or Cancel. The operator indicates his
choice by touching the button of
choice. The system then takes the
appropriate action and the button
typically disappears.
DynaView
consists of various
screens, each meant to serve a
unique purpose of the machine being
served. Tabs are shown row across
the top of the display. The user
selects a screen of information by
touching the appropriate tab. The
folder that is selected will be brought
to the front so it’s contents are
visable
The main body of the screen is used
for description text, data, setpoints,
or keys (touch sensitive areas) The
double up arrows cause a page by
page scroll either up or down. The
single arrow causes a line by line
scroll to occur. At the end of the
screen, the appropriate scroll buttons
will disappear. Wrap around will not
occur.
The bottom of the screen is the
persistent area. It is present in all
screens and performs the following
functions. The left circular area is
used to reduce the contrast and
viewing angle of the display. The
right circular area is used to increase
the contrast and viewing angle of the
display. The contrast control will be
limited to avoid complete “light” or
complete “dark”, which would
potentially confuse an unfamiliar
user to thinking the display was
malfunctioning.