Trane CVHE-SVU01E-ENX39640712050 Water Dispenser User Manual


 
CVHE-SVU01E-EN
36
Operator
Interface
The chilled water reset status area in
the right most column will display
one of the following messages:
Return, Constant Return, Outdoor,
None
The left column text “Front Panel”,
“BAS”, “External”, Chilled Water
Reset, and “Active Chilled Water
Setpoint” will always be present
regardless of installation or enabling
those optional items. In the second
column “- - - -” will be shown if that
option is Not Installed, otherwise the
current setpoint from that source will
be shown.
The “Back” button provides
navigation back to the chiller screen.
The active chilled water setpoint is
the setpoint that is currently in use. It
will be displayed to 0.1 degrees
Fahrenheit or Celsius. Touching the
double arrow to the left of the Active
Chilled Water Setpoint will take the
user to the active chilled water
setpoint arbitration sub-screen.
The Active Chilled Water Setpoint
the result of arbitration between the
front panel, BAS, and external
setpoints,