The left column text “Front Panel”,
“BAS”, “External”, and “Active
Current Limit Setpoint” will always
be present regardless of installation
or enabling those optional items. In
the second column “- - - -” will be
shown if that option is Not Installed,
otherwise the current setpoint from
that source will be shown. The
“Back” button provides navigation
back to the chiller screen.
Note: This is the same for other
setpoints in the “Main” menu.
The active current limit setpoint is
the current limit setpoint that is
currently in use. It will be displayed
in percent RLA. Touching the double
arrow to the left of the Active Current
Limit Setpoint will take the user to
the active current limit setpoint sub-
screen. The active current limit
setpoint is that setpoint to which the
unit is currently controlling. It is the
result of arbitration between the front
panel, BAS, and external setpoints.