Figure 27. Cutout strategy
Machine Protection
and Adaptive
Control
Limit Loading: The potential to limit loading increases as the saturated
evaporator temperature approaches the evaporator limit setpoint.
Unload: The potential to unload increases as the saturated evaporator
temperature falls further below the evaporator limit setpoint.
Figure 27 illustrates these functions
as follows:
• chilled water setpoint
• evap leaving water temp cutout
• evap rfgt temp output