Trane CVHE-SVU01E-ENX39640712050 Water Dispenser User Manual


 
33
CVHE-SVU01E-EN
Operator
Interface
Reference
Top Level Mode Sub Level Mode BAS Code
Waiting To Start Motor Temperature Inhibit: Motor Temperature / Inhibit Temperature 70
Waiting To Start Restart Time Inhibit: MIN:SEC 70
Waiting To Start High Vacuum Inhibit: Oil Sump Press / Inhibit Press 70
Waiting To Start Low Oil Temperature Inhibit: Oil Temperature / Inhibit Temperature 70
Waiting To Start Waiting For Starter To Start: MIN:SEC 70
Starting Compressor There is no sub mode displayed 72
Running There is no sub mode displayed 74
Running Hot Water Control 74
Running Surge 74
Running Base Loaded 74
Running Hot Gas Bypass 74
Running Ice Building 74
Running Ice To Normal Transition 74
Running Current Control Soft Loading 74
Running Capacity Control Soft Loading 74
Running – Limit Current Limit 75
Running – Limit Phase Unbalance Limit 75
Running – Limit Condenser Pressure Limit 75
Running – Limit Evaporator Temperature Limit 75
Running – Limit Minimum Capacity Limit 75
Running – Limit Maximum Capacity Limit 75
Free Cooling 09
Free Cooling Opening Free Cooling Valves 09
Free Cooling Closing Free Cooling Valves 09
Preparing To
Shutdown Closing IGV: IGV Position % 7E
Shutting Down Post-Lubrication Time: MIN:SEC 7E
Shutting Down Evaporator Pump Off Delay: MIN:SEC 7E
Shutting Down Condenser Pump Off Delay: MIN:SEC 7E