19
RLC-PRC005-E4
Performance Data
Standard Units (SI Units)
Table P-1 — RTAC 140 Entering Condenser Air Temperature (°C)
LWT 25 30 35 4 0 46 50
°C C.C. P.I. COP C.C. P.I. COP C.C. P.I. COP C.C. P.I. COP C.C. P.I. COP C.C. P.I. COP
kW kW/kW kW kW kW/kW kW kW kW/kW kW kW kW/kW kW kW kW/kW kW kW kW/kW kW
5 536.3 131.3 3.65 505.7 141.8 3.21 474.1 153.5 2.80 441.6 166.5 2.42 400.7 184.0 2.01 374.2 196.1 1.77
7 571.1 136.4 3.75 539.0 147.1 3.31 505.9 159.0 2.90 471.7 172.1 2.51 428.8 189.8 2.09 400.9 202.1 1.84
9 606.9 141.7 3.85 573.2 152.6 3.41 538.4 164.6 2.99 502.6 177.9 2.60 457.6 195.8 2.16 409.6 197.1 1.92
11 643.4 147.2 3.95 608.1 158.2 3.50 571.7 170.4 3.07 534.2 183.9 2.68 486.9 202.0 2.24 417.2 191.3 2.01
13 680.6 152.8 4.04 643.7 164.0 3.58 605.6 176.4 3.15 566.3 190.0 2.75 509.4 204.9 2.31 423.3 184.6 2.11
Table P-2 — RTAC 155 Entering Condenser Air Temperature (°C)
LWT 25 30 35 4 0 46 50
°C C.C. P.I. COP C.C. P.I. COP C.C. P.I. COP C.C. P.I. COP C.C. P.I. COP C.C. P.I. COP
kW kW/kW kW kW kW/kW kW kW kW/kW kW kW kW/kW kW kW kW/kW kW kW kW/kW kW
5 587.8 145.8 3.60 554.5 156.9 3.18 520.0 169.4 2.78 484.5 183.2 2.41 440.0 201.9 2.00 411.0 214.9 1.77
7 625.7 151.7 3.70 590.6 163.0 3.27 554.4 175.6 2.87 517.1 189.6 2.50 470.2 208.5 2.08 439.7 221.7 1.84
9 664.3 157.8 3.79 627.5 169.3 3.36 589.5 182.0 2.95 550.3 196.2 2.57 501.1 215.3 2.15 450.5 217.4 1.92
11 703.7 164.1 3.87 665.1 175.7 3.44 625.3 188.7 3.03 584.2 203.0 2.65 532.6 222.3 2.22 454.9 209.3 2.00
13 743.7 170.6 3.95 703.4 182.4 3.52 661.7 195.5 3.10 618.7 209.9 2.72 561.8 225.5 2.31 461.3 202.5 2.10
Table P-3 — RTAC 170 Entering Condenser Air Temperature (°C)
LWT 25 30 35 4 0 46 50
°C C.C. P.I. COP C.C. P.I. COP C.C. P.I. COP C.C. P.I. COP C.C. P.I. COP C.C. P.I. COP
kW kW/kW kW kW kW/kW kW kW kW/kW kW kW kW/kW kW kW kW/kW kW kW kW/kW kW
5 640.2 160.5 3.56 603.9 172.2 3.15 566.5 185.4 2.77 527.9 200.0 2.41 479.5 220.0 2.00 448.1 233.9 1.77
7 681.1 167.2 3.65 642.9 179.1 3.24 603.5 192.4 2.85 562.9 207.2 2.48 511.9 227.4 2.07 478.8 241.4 1.84
9 722.7 174.2 3.73 682.6 186.2 3.32 641.2 199.7 2.93 598.6 214.6 2.56 545.0 234.9 2.14 491.5 237.7 1.91
11 765.0 181.4 3.81 723.0 193.5 3.39 679.5 207.2 3.00 634.9 222.2 2.63 578.7 242.7 2.21 497.9 230.3 1.99
13 807.9 188.8 3.88 763.9 201.1 3.46 718.5 214.8 3.07 671.8 230.0 2.69 607.7 245.1 2.30 504.4 222.7 2.08
Table P-4 — RTAC 185 Entering Condenser Air Temperature (°C)
LWT 25 30 35 4 0 46 50
°C C.C. P.I. COP C.C. P.I. COP C.C. P.I. COP C.C. P.I. COP C.C. P.I. COP C.C. P.I. COP
kW kW/kW kW kW kW/kW kW kW kW/kW kW kW kW/kW kW kW kW/kW kW kW kW/kW kW
5 708.2 177.3 3.57 669.4 190.2 3.16 629.1 204.6 2.78 587.4 220.8 2.43 534.9 242.8 2.03 500.5 258.0 1.79
7 753.1 184.7 3.66 712.2 197.8 3.25 669.8 212.5 2.86 625.9 228.9 2.50 570.5 251.2 2.09 525.9 261.3 1.86
9 798.8 192.3 3.74 755.9 205.7 3.33 711.3 220.6 2.94 665.2 237.3 2.57 607.0 259.9 2.16 539.2 256.9 1.94
11 845.3 200.2 3.81 800.3 213.8 3.40 753.6 229.0 3.01 705.3 245.9 2.64 644.2 268.9 2.22 548.1 249.3 2.03
13 892.5 208.4 3.88 845.4 222.2 3.47 796.6 237.6 3.08 746.1 254.8 2.70 672.6 271.9 2.29 551.0 238.7 2.12
Table P-5 — RTAC 200 Entering Condenser Air Temperature (°C)
LWT 25 30 35 4 0 46 50
°C C.C. P.I. COP C.C. P.I. COP C.C. P.I. COP C.C. P.I. COP C.C. P.I. COP C.C. P.I. COP
kW kW/kW kW kW kW/kW kW kW kW/kW kW kW kW/kW kW kW kW/kW kW kW kW/kW kW
5 777.8 194.3 3.58 736.2 208.3 3.18 692.9 224.2 2.80 647.9 241.8 2.44 591.0 265.7 2.04 553.7 282.4 1.81
7 827.0 202.4 3.66 783.1 216.7 3.26 737.4 232.9 2.88 690.1 250.8 2.52 630.0 275.3 2.11 580.4 285.5 1.88
9 877.0 210.8 3.75 830.9 225.5 3.34 782.9 241.9 2.95 733.1 260.2 2.59 670.1 285.1 2.17 588.7 276.7 1.96
11 928.0 219.5 3.82 879.7 234.5 3.41 829.4 251.3 3.02 777.2 270.0 2.65 711.0 295.4 2.23 598.7 268.6 2.05
13 979.8 228.5 3.89 929.3 243.8 3.48 876.7 260.9 3.08 822.1 280.0 2.71 741.1 298.2 2.31 607.0 258.8 2.15
Notes :
1. Ratings based on sea level altitude and evaporator fouling factor of 0.0176 m²°K/kW.
2. Consult Trane representative for performance at temperatures outside of the ranges shown.
3. P.I. kW = compressor power input only.
4. COP = Coefficient of Performance (kW/kW). Power input includes compressors, condenser fans and control power.
5. Ratings are based on an evaporator temperature drop of 6°C.
6. Interpolation between points is permissible. Extrapolation is not permitted.
7. Above 40°C ambient, the units will have the High-Ambient option.
8. Shaded area reflects Adaptive Control™ Microprocessor control algorithms.