Trane RTAC 120 to 200 Refrigerator User Manual


 
30
RLC-PRC005-E4
Performance Data
Table P-48 — RTAC 200 Entering Condenser Air Temperature (°F)
LWT 7 7 86 9 5 104 115
°F C.C.Ton P.I. kW EER C.C.Ton P.I. kW EER C.C.Ton P.I. kW EER C.C.Ton P.I. kW EER C.C.Ton P.I. kW EER
41 220.8 202.6 12.32 208.3 217.3 10.87 195.4 233.7 9.52 182.0 251.9 8.26 165.2 276.6 6.86
44 232.3 210.1 12.52 219.2 225.1 11.07 205.7 241.8 9.70 191.7 260.3 8.43 174.1 285.4 7.01
45 236.2 212.6 12.58 222.9 227.7 11.13 209.1 244.6 9.76 195.0 263.2 8.48 176.7 287.4 7.07
46 240.1 215.3 12.64 226.6 230.4 11.19 212.6 247.4 9.81 198.2 266.1 8.53 178.8 288.1 7.14
48 247.9 220.5 12.76 234.0 235.8 11.30 219.6 253.0 9.92 204.8 272.0 8.64 182.9 289.5 7.27
Notes :
1. Ratings based on sea level altitude and evaporator fouling factor of 0.0176 m²°K/kW.
2. Consult Trane representative for performance at temperatures outside of the ranges shown.
3. P.I. kW = compressor power input only.
4. COP = Coefficient of Performance (kW/kW). Power input includes compressor, condenser fans and control power.
5. Ratings are based on an evaporator temperature drop of 6°C.
6. Interpolation between points is permissible. Extrapolation is not permitted.
7. Above 40°C ambient, the units will have the High-Ambient option.
8. Shaded area reflects Adaptive Control Microprocessor control algorithms.