Trane RTAC 120 to 200 Refrigerator User Manual


 
25
RLC-PRC005-E4
Performance Data
Standard Units (English Units)
Table P-25
RTAC 140 Entering Condenser Air Temperature (°F)
LWT 77 86 95 104 115 122
°F C.C. P.I. EER C.C. P.I. EER C.C. P.I. EER C.C. P.I. EER C.C. P.I. EER C.C. P.I. EER
To n k W To n k W To n k W To n k W Ton k W To n k W
41 152.5 131.3 12.45 143.8 141.8 10.96 134.8 153.5 9.56 125.6 166.5 8.27 114.0 184.0 6.85 106.4 196.1 6.03
44 160.8 135.5 12.75 151.7 146.2 11.24 142.4 158.1 9.83 132.7 171.2 8.52 120.6 188.9 7.08 112.8 201.1 6.24
45 163.6 137.0 12.85 154.4 147.7 11.34 144.9 159.6 9.92 135.1 172.8 8.60 122.9 190.5 7.15 114.3 201.5 6.31
46 166.4 138.5 12.95 157.1 149.2 11.43 147.5 161.2 10.00 137.6 174.4 8.68 125.1 192.2 7.22 115.0 200.1 6.39
48 172.0 141.4 13.14 162.5 152.3 11.61 152.6 164.3 10.17 142.5 177.6 8.84 129.7 195.5 7.37 116.3 197.4 6.55
Table P-26 — RTAC 155 Entering Condenser Air Temperature (°F)
LWT 77 86 95 104 115 122
°F C.C. P.I. EER C.C. P.I. EER C.C. P.I. EER C.C. P.I. EER C.C. P.I. EER C.C. P.I. EER
To n k W To n k W To n k W To n k W Ton k W To n k W
41 167.2 145.8 12.28 157.7 156.9 10.84 147.9 169.4 9.49 137.8 183.2 8.24 125.1 201.9 6.84 116.9 214.9 6.03
44 176.2 150.7 12.56 166.3 162.0 11.11 156.0 174.6 9.74 145.5 188.5 8.47 132.3 207.4 7.05 123.7 220.6 6.23
45 179.2 152.4 12.65 169.1 163.7 11.20 158.8 176.3 9.83 148.1 190.3 8.55 134.7 209.3 7.12 125.4 221.2 6.30
46 182.2 154.1 12.74 172.1 165.4 11.28 161.6 178.1 9.91 150.7 192.1 8.62 137.2 211.2 7.19 126.2 220.0 6.38
48 188.3 157.5 12.91 177.9 168.9 11.44 167.1 181.7 10.06 156.0 195.8 8.77 142.0 214.9 7.33 127.9 217.6 6.53
Table P-27 — RTAC 170 Entering Condenser Air Temperature (°F)
LWT 77 86 95 104 115 122
°F C.C. P.I. EER C.C. P.I. EER C.C. P.I. EER C.C. P.I. EER C.C. P.I. EER C.C. P.I. EER
To n k W To n k W To n k W To n k W Ton k W To n k W
41 182.1 160.5 12.14 171.8 172.2 10.75 161.1 185.4 9.44 150.2 200.0 8.21 136.4 220.0 6.83 127.4 233.9 6.04
44 191.8 166.1 12.40 181.0 177.9 11.00 169.9 191.2 9.67 158.4 206.0 8.43 144.1 226.1 7.04 134.7 240.1 6.23
45 195.0 168.0 12.48 184.1 179.9 11.08 172.8 193.2 9.75 161.2 208.0 8.50 146.6 228.2 7.10 136.5 241.0 6.29
46 198.3 170.0 12.56 187.2 181.9 11.16 175.8 195.2 9.82 164.0 210.1 8.57 149.3 230.3 7.17 137.5 240.0 6.36
48 204.9 173.8 12.72 193.5 185.8 11.31 181.8 199.3 9.97 169.7 214.2 8.71 154.5 234.5 7.30 139.5 237.9 6.51
Table P-28 — RTAC 185 Entering Condenser Air Temperature (°F)
LWT 77 86 95 104 115 122
°F C.C. P.I. EER C.C. P.I. EER C.C. P.I. EER C.C. P.I. EER C.C. P.I. EER C.C. P.I. EER
To n k W To n k W To n k W To n k W Ton k W To n k W
41 201.4 177.3 12.17 190.4 190.2 10.80 178.9 204.6 9.50 167.1 220.8 8.28 152.1 242.8 6.91 142.4 258.0 6.11
44 212.1 183.4 12.43 200.5 196.5 11.04 188.6 211.2 9.73 176.2 227.5 8.49 160.6 249.8 7.11 148.3 260.8 6.31
45 215.6 185.5 12.51 203.9 198.6 11.12 191.8 213.4 9.80 179.3 229.8 8.56 163.4 252.1 7.17 150.0 260.8 6.38
46 219.3 187.6 12.59 207.4 200.8 11.20 195.1 215.7 9.88 182.4 232.1 8.63 166.3 254.6 7.23 151.0 259.6 6.45
48 226.5 191.9 12.74 214.3 205.2 11.35 201.6 220.2 10.02 188.6 236.8 8.76 172.1 259.4 7.35 153.1 257.1 6.60
Table P-29 — RTAC 200 Entering Condenser Air Temperature (°F)
LWT 77 86 95 104 115 122
°F C.C. P.I. EER C.C. P.I. EER C.C. P.I. EER C.C. P.I. EER C.C. P.I. EER C.C. P.I. EER
To n k W To n k W To n k W To n k W Ton k W To n k W
41 221.2 194.3 12.21 209.4 208.3 10.85 197.1 224.2 9.56 184.3 241.8 8.34 168.1 265.7 6.98 157.5 282.4 6.18
44 232.9 201.0 12.46 220.5 215.3 11.09 207.6 231.4 9.78 194.3 249.3 8.55 177.3 273.7 7.17 163.8 285.0 6.38
45 236.8 203.3 12.54 224.2 217.7 11.17 211.2 233.9 9.85 197.6 251.9 8.62 180.5 276.3 7.23 165.3 284.5 6.45
46 240.7 205.7 12.62 228.0 220.1 11.24 214.8 236.4 9.93 201.0 254.5 8.69 183.6 279.1 7.29 166.0 282.1 6.53
48 248.6 210.3 12.77 235.6 225.0 11.39 221.9 241.4 10.06 207.8 259.7 8.81 189.9 284.6 7.40 167.3 277.2 6.68
Notes :
1. Ratings based on sea level altitude and evaporator fouling factor of 0.0176 m²°K/kW.
2. Consult Trane representative for performance at temperatures outside of the ranges shown.
3. P.I. kW = compressor power input only.
4. COP = Coefficient of Performance (kW/kW). Power input includes compressors, condenser fans and control power.
5. Ratings are based on an evaporator temperature drop of 6°C.
6. Interpolation between points is permissible. Extrapolation is not permitted.
7. Above 40°C ambient, the units will have the High-Ambient option.
8. Shaded area reflects Adaptive Control™ Microprocessor control algorithms.