Trane RTAC 120 to 200 Refrigerator User Manual


 
24
RLC-PRC005-E4
Performance Data
Low Noise HE Units (SI Units)
Table P-24
RTAC 200 Entering Condenser Air Temperature (°C)
LWT 25 30 35 40 46
°C C.C. P.I. COP C.C. P.I. COP C.C. P.I. COP C.C. P.I. COP C.C. P.I. COP
kW kW kW/kW kW kW kW/kW kW kW kW/kW kW kW kW/kW kW kW kW/kW
5 776.4 202.6 3.61 732.4 217.3 3.19 686.9 233.7 2.79 640.1 251.9 2.42 581.1 276.6 2.01
7 824.9 211.6 3.68 778.4 226.6 3.25 730.3 243.4 2.85 680.8 262.0 2.48 618.6 287.2 2.06
9 874.3 221.0 3.74 825.2 236.4 3.31 774.5 253.6 2.91 722.4 272.5 2.53 644.6 289.6 2.13
11 924.4 230.8 3.80 872.8 246.5 3.37 819.5 264.1 2.96 764.6 283.5 2.58 654.7 281.3 2.23
13 975.2 240.9 3.85 921.0 257.1 3.42 865.1 275.1 3.01 807.5 294.9 2.63 665.5 272.6 2.33
Notes :
1. Ratings based on sea level altitude and evaporator fouling factor of 0.0176 m²°K/kW.
2. Consult Trane representative for performance at temperatures outside of the ranges shown.
3. P.I. kW = compressor power input only.
4. COP = Coefficient of Performance (kW/kW). Power input includes compressors, condenser fans and control power.
5. Ratings are based on an evaporator temperature drop of 6°C.
6. Interpolation between points is permissible. Extrapolation is not permitted.
7. Above 40°C ambient, the units will have the High-Ambient option.
8. Shaded area reflects Adaptive Control™ Microprocessor control algorithms.