22
RLC-PRC005-E4
Performance Data
Low Noise Standard Units (SI Units)
Table P-13 RTAC 140 Entering Condenser Air Temperature (°C)
LWT 25 30 35 40
°C C.C. kW P.I. kW COP kW/kW C.C. kW P.I. kW COP kW/kW C.C. kW P.I. kW COP kW/kW C.C. kW P.I. kW COP kW/kW
5 510.3 144.5 3.36 478.7 156.3 2.92 446.2 169.3 2.52 412.9 183.5 2.16
7 541.1 150.7 3.42 507.9 162.7 2.98 473.7 175.9 2.58 438.8 190.4 2.22
9 572.3 157.1 3.48 537.4 169.4 3.04 501.6 182.8 2.64 465.3 197.4 2.27
11 603.8 163.7 3.53 567.3 176.2 3.09 529.7 189.9 2.68 491.5 204.7 2.32
13 635.6 170.6 3.57 597.3 183.3 3.13 558.0 197.2 2.73 509.0 205.6 2.39
Table P-14
RTAC 155 Entering Condenser Air Temperature (°C)
LWT 25 30 35 40
°C C.C. kW P.I. kW COP kW/kW C.C. kW P.I. kW COP kW/kW C.C. kW P.I. kW COP kW/kW C.C. kW P.I. kW COP kW/kW
5 560.0 159.7 3.33 525.5 172.2 2.91 490.0 186.1 2.52 453.8 201.2 2.16
7 593.4 166.7 3.39 557.0 179.5 2.97 519.8 193.5 2.57 481.6 208.9 2.22
9 627.1 173.9 3.44 588.9 186.9 3.02 549.8 201.2 2.62 509.8 216.8 2.26
11 661.1 181.4 3.48 621.1 194.7 3.06 580.0 209.2 2.67 538.1 224.9 2.31
13 695.3 189.1 3.52 653.4 202.6 3.10 610.5 217.3 2.71 556.8 225.9 2.38
Table P-15 — RTAC 170 Entering Condenser Air Temperature (°C)
LWT 25 30 35 40
°C C.C. kW P.I. kW COP kW/kW C.C. kW P.I. kW COP kW/kW C.C. kW P.I. kW COP kW/kW C.C. kW P.I. kW COP kW/kW
5 610.3 175.1 3.31 572.8 188.3 2.90 534.3 203.0 2.52 494.8 219.1 2.17
7 646.3 182.9 3.36 606.8 196.4 2.95 566.2 211.3 2.57 524.8 227.7 2.22
9 682.6 191.0 3.41 641.1 204.7 3.00 598.4 219.9 2.61 555.0 236.3 2.26
11 719.1 199.4 3.45 675.6 213.3 3.04 630.9 228.6 2.65 585.5 245.3 2.30
13 755.8 208.0 3.48 710.2 222.1 3.07 663.5 237.6 2.69 604.8 246.2 2.37
Table P-16
RTAC 185 Entering Condenser Air Temperature (°C)
LWT 25 30 35 40
°C C.C. kW P.I. kW COP kW/kW C.C. kW P.I. kW COP kW/kW C.C. kW P.I. kW COP kW/kW C.C. kW P.I. kW COP kW/kW
5 675.9 193.4 3.32 635.4 208.0 2.91 593.7 224.3 2.53 550.9 242.1 2.19
7 715.5 202.1 3.37 672.8 217.1 2.96 628.9 233.6 2.58 583.8 251.7 2.23
9 755.4 211.1 3.42 710.6 226.4 3.01 664.4 243.3 2.62 615.2 261.0 2.27
11 795.7 220.5 3.45 748.6 236.1 3.04 700.2 253.3 2.66 648.6 271.3 2.31
13 836.2 230.1 3.48 787.0 246.1 3.07 736.3 263.7 2.69 668.0 271.0 2.38
Table P-17 — RTAC 200 Entering Condenser Air Temperature (°C)
LWT 25 30 35 40
°C C.C. kW P.I. kW COP kW/kW C.C. kW P.I. kW COP kW/kW C.C. kW P.I. kW COP kW/kW C.C. kW P.I. kW COP kW/kW
5 742.7 212.0 3.33 699.2 228.1 2.93 654.1 245.8 2.55 607.7 265.2 2.20
7 786.1 221.6 3.38 740.1 238.0 2.97 692.6 256.2 2.59 643.7 276.1 2.24
9 829.9 231.6 3.42 781.5 248.5 3.01 731.6 267.1 2.63 680.5 287.3 2.28
11 874.1 242.0 3.46 823.3 259.3 3.05 771.0 278.4 2.66 717.1 299.2 2.31
13 918.6 252.8 3.48 865.5 270.6 3.07 810.6 290.2 2.69 730.4 292.2 2.41
Notes :
1. Ratings based on sea level altitude and evaporator fouling factor of 0.0176 m²°K/kW.
2. Consult Trane representative for performance at temperatures outside of the ranges shown.
3. P.I. kW = compressor power input only.
4. COP = Coefficient of Performance (kW/kW). Power input includes compressors, condenser fans and control power.
5. Ratings are based on an evaporator temperature drop of 6°C.
6. Interpolation between points is permissible. Extrapolation is not permitted.
7. Above 40°C ambient, the units will have the High-Ambient option.
8. Shaded area reflects Adaptive Control™ Microprocessor control algorithms.