Electrical Data
46
RLC-PRC005-E4
Table E-1
—
Electrical Data 400/3/50
Motor Data Option
Compressor (Each) Fans (Each) Control Evaporator
Max Amps (1) Starting Amps (2) Fans Fuse Heater
Quantity Circuit 1 Circuit 2 Circuit 1 Circuit 2 Quantity kW FLA Size (A) VA A kW
Standard
2 180 180 251 251 8 1.88 4.5 80 860 2.15 0.5
2 214 180 271 251 9 1.88 4.5 80 860 2.15 0.5
2 214 214 271 271 10 1.88 4.5 80 860 2.15 0.5
2 259 214 330 271 11 1.88 4.5 80 860 2.15 0.5
2 259 259 330 330 12 1.88 4.5 80 860 2.15 0.5
Standard Low Noise
2 180 180 251 251 8 0.85 2.6 80 860 2.15 0.5
2 214 180 271 251 9 0.85 2.6 80 860 2.15 0.5
2 214 214 271 271 10 0.85 2.6 80 860 2.15 0.5
2 259 214 330 271 11 0.85 2.6 80 860 2.15 0.5
2 259 259 330 330 12 0.85 2.6 80 860 2.15 0.5
High Efficiency
2 146 146 214 214 8 1.88 4.5 80 860 2.15 0.5
2 180 146 251 214 9 1.88 4.5 80 860 2.15 0.5
2 180 180 251 251 10 1.88 4.5 80 860 2.15 0.5
2 214 178 271 251 11 1.88 4.5 80 860 2.15 0.5
2 214 214 271 271 12 1.88 4.5 80 860 2.15 0.5
2 259 214 330 271 13 1.88 4.5 80 860 2.15 0.5
2 259 259 330 330 14 1.88 4.5 80 860 2.15 0.5
High Efficiency Low Noise
2 146 146 214 214 8 0.85 2.6 80 860 2.15 0.5
2 180 146 251 214 9 0.85 2.6 80 860 2.15 0.5
2 180 180 251 251 10 0.85 2.6 80 860 2.15 0.5
2 214 178 271 251 11 0.85 2.6 80 860 2.15 0.5
2 214 214 271 271 12 0.85 2.6 80 860 2.15 0.5
2 259 214 330 271 13 0.85 2.6 80 860 2.15 0.5
2 259 259 330 330 14 0.85 2.6 80 860 2.15 0.5
Notes:
1. Maximum FLA per compressor.
2. Compressors starting amps, Star delta start.