Trane RTAC 120 to 200 Refrigerator User Manual


 
27
RLC-PRC005-E4
Performance Data
Table P-36
RTAC 200 Entering Condenser Air Temperature (°F)
LWT 77 86 95 104 115 122
°F C.C. P.I. EER C.C. P.I. EER C.C. P.I. EER C.C. P.I. EER C.C. P.I. EER C.C. P.I. EER
Ton kW EER Ton kW EER Ton kW EER Ton kW EER Ton kW EER Ton kW EER
232.6 8.83 174.7 255.4 7.42 159.3 278.4 6.26
44 241.2 194.9 13.04 228.6 208.1 11.67 215.5 223.0 10.34 202.0 239.8 9.08 184.9 262.8 7.65 168.7 286.2 6.46
45 245.5 197.1 13.14 232.7 210.3 11.76 219.4 225.4 10.43 205.7 242.2 9.17 188.3 265.4 7.73 171.5 288.1 6.53
46 249.8 199.4 13.24 236.8 212.7 11.86 223.4 227.8 10.52 209.4 244.7 9.25 191.8 268.0 7.80 173.9 288.9 6.61
48 258.5 204.0 13.43 245.1 217.3 12.04 231.3 232.6 10.69 216.9 249.7 9.41 198.8 273.1 7.95 178.6 290.4 6.75
Notes :
1. Ratings based on sea level altitude and evaporator fouling factor of 0.0176 m²°K/kW.
2. Consult Trane representative for performance at temperatures outside of the ranges shown.
3. P.I. kW = compressor power input only.
4. COP = Coefficient of Performance (kW/kW). Power input includes compressors, condenser fans and control power.
5. Ratings are based on an evaporator temperature drop of 6°C.
6. Interpolation between points is permissible. Extrapolation is not permitted.
7. Above 40°C ambient, the units will have the High-Ambient option.
8. Shaded area reflects Adaptive Control™ Microprocessor control algorithms.