Trane RTAC 120 to 200 Refrigerator User Manual


 
21
RLC-PRC005-E4
Performance Data
High Efficiency Units (SI Units)
Table P-12
RTAC 200 Entering Condenser Air Temperature (°C)
LWT 2 5 30 35 40 46 52
°C C.C. P.I. COP C.C. P.I. COP C.C. P.I. COP C.C. P.I. COP C.C. P.I. COP C.C. P.I. COP
kW kW kW/kW kW kW kW/kW kW kW kW/kW kW kW kW/kW kW kW kW/kW kW kW kW/kW
5 803.3 188.3 3.73 761.2 201.3 3.33 717.3 216.1 2.95 671.8 232.6 2.59 614.2 255.4 2.17 560.1 278.4 1.83
7 856.9 196.2 3.84 812.3 209.4 3.44 766.0 224.4 3.05 717.9 241.2 2.68 657.1 264.3 2.26 600.0 287.8 1.91
9 911.8 204.4 3.94 864.8 217.8 3.53 816.0 233.0 3.14 765.4 250.2 2.76 701.3 273.7 2.33 629.6 290.6 1.98
11 968.0 212.9 4.04 918.6 226.5 3.62 867.3 242.0 3.22 814.1 259.4 2.84 746.8 283.3 2.41 642.5 283.5 2.07
13 1025.5 221.6 4.12 973.7 235.5 3.71 919.9 251.2 3.31 864.1 269.0 2.92 793.5 293.3 2.48 648.9 272.4 2.17
Notes :
1. Ratings based on sea level altitude and evaporator fouling factor of 0.0176 m²°K/kW.
2. Consult Trane representative for performance at temperatures outside of the ranges shown.
3. P.I. kW = compressor power input only.
4. COP = Coefficient of Performance (kW/kW). Power input includes compressors, condenser fans and control power.
5. Ratings are based on an evaporator temperature drop of 6°C.
6. Interpolation between points is permissible. Extrapolation is not permitted.
7. Above 40°C ambient, the units will have the High-Ambient option.
8. Shaded area reflects Adaptive Control™ Microprocessor control algorithms.