Xantrex Technology 815-2012 Microwave Oven User Manual


 
52 Freedom SW Owner’s Guide
Configuring the Freedom SW using the SCP
Battery Charger Functions
When AC power is available, the Freedom SW can operate as a
battery charger. Different battery types and chemistries require
different charging voltage levels. Not charging batteries at the
required levels can shorten battery life or damage the batteries. The
Freedom SW is configured at the factory to work with the battery
types recommended for inverter applications. If the default settings
do not work for your specific installation, you can adjust the charge
stage settings (as recommended by the battery manufacturer) on the
Custom (Battery) Settings menu (see page 53).
Table 11 Charger Settings Menu Description
Item Description
Batt Type
Sets the system battery chemistry and type:
Flooded
,
AGM
,
Gel
, and
Custom
.
Selecting Custom displays the Custom Settings item, which allows you to
adjust the settings for each charging stage.
Custom
Settings
Displays the Custom Battery Settings menu, where you can adjust
settings specific to your battery type and installation. It is only displayed if
Custom is selected as the Batt Type.
Batt
Capacity
Selects the system battery capacity in amp hours. Setting the battery capacity to
0 resets the charging current to its default values. Zero Ah battery capacity
implies there is no absorption exit current criteria and absorption only exits
when the absorption timer (default 3hrs, range 1min-8hr) expires.
Max Chg
Rate
Sets the percentage of the maximum DC output current that is available to the
charger. The maximum DC output current for different models is:
Freedom SW 2012 —100 ADC
Freedom SW 3012 —150 ADC
Freedom SW 2024 —50 ADC
Freedom SW 3024 —75 ADC
If two Freedom SWs are charging the same battery bank, set each inverter's
Max Chg Rate to 1/n of the desired charge rate (where n is the number of
inverter/chargers).
Charge
Cycle
Sets the charging method: 3Stage (bulk, absorption, float) or 2StgNoFloat
(bulk, absorption, no float).
ReCharge
Volts
Sets the recharging volts to tell the charger to initiate charging when the battery
drains past the value setting.
Auto
ReCharge
Enables or disables automatic charging. When there are two or more power
sources for charging batteries, Auto ReCharge can be disabled to allow
manual charging of batteries.
Absorb
Time
Sets the maximum time spent in the absorption stage, before transitioning to float
or no float.
NOTE
: The Absorb Time setting resets to its default value of 180 minutes when
the Battery Type is changed except when changing to Custom Settings. In Custom
Settings, the Absorb Time setting will not reset to its default value.
Default
Batt Temp
Selects the battery temperature charging compensation if a battery temperature
sensor is not installed. In the absence of a battery temperature sensor, the
charger uses one of three settings:
Cold
(5 °C/41 °F),
Warm
(25 °C/77 °F), or
Hot
(40 °C/104 °F).
NOTE:
This information is provided for guidance only. Variations in battery
chemistry and site-specific environmental considerations mean that you
should consult your system designer or battery manufacturer for specific
recommendations for appropriate battery voltage and current settings.
Table 11 Charger Settings Menu Description
Item Description
Freedom SW 3K2K InvChg Owners Guide.book Page 52 Thursday, July 31, 2014 1:42 PM