Carrier 30HW018-040 Refrigerator User Manual


 
Table 14 Troubleshooting (cont)
SYMPTOMS CAUSE REMEDY
Compressor
loses oil
Leak in system Repair leak.
Mechanical damage (blown piston or broken
discharge valve)
Repair damage or replace compressor as needed.
Oil trapped in line Check piping for oil traps.
Crankcase heater not energized
during shutdown
Check wiring and crankcase heater contacts on the
temperature controller, and replace heater if necessary.
Hot liquid line Shortage of refrigerant due to leak Repair leak and recharge.
Frosted liquid line Shutoff valve partially closed or restricted Open valve or remove restriction.
Restricted filter drier Replace filter drier.
Frosted suction line Expansion valve admitting excess refrigerant Adjust expansion valve. Replace valve if defective.
Compressor will
not unload
Burned-out coil Replace coil.
Defective capacity control valve Replace valve.
Miswired solenoid Rewire correctly.
Weak, broken, or wrong valve body spring Replace spring.
Compressor will
not load
Miswired solenoid Rewire correctly.
Defective capacity control valve Replace valve.
Plugged strainer (high side) Clean or replace strainer.
Stuck or damaged unloader piston or piston ring(s) Clean or replace the necessary parts.
System noises Piping vibration Support piping as required.
Check for loose pipe connectors.
Expansion valve hissing Add refrigerant.
Check for plugged liquid line strainer.
Compressor noisy Check valve plates for valve noise.
Replace compressor (worn bearings).
Check for loose compressor holddown bolts.
Freeze-up Improper charging Make sure a full quantity of fluid is flowing through the
cooler while charging, and suction pressure in cooler is
equal to or greater than pressure corresponding to 32 F
(0° C) (58 psig [400 kPa] for Refrigerant 22).
Improperly set safety thermostat Check safety thermostat for proper setting at beginning of
each season.
Operating with safety thermostat bypassed If thermostat was bypassed for checking, be sure it is back
in circuit before starting unit.
Improper circulation of condenser water Use adequately sized cleanable strainer in the condenser
water circuit. Make sure strainer is clean. It may sometimes
be necessary to chemically treat the water to prevent for-
mation of deposits.
System not drained for winter shutdown Remove drain plugs at end of cooling season. Blow out any
residual water. Instead of draining, a suitable anti-freeze
may be added to the water.
Damage to chiller due to freez-
ing is considered abuse and is not covered by warranty.
Loose Thermistor Tighten thermistor to pipe and reinsulate (30HW).
39