Models H62 & H63To the Installer
111012
Air Cooled Units
DO NOT obstruct air intake and discharge openings:
Air cooled units require a minimum of 6” (152 mm) of
clearance around all sides of the freezer and 7--1/2”
(191 mm) on the bottom to allow for adequate air flow
across the condenser . Failure to allow adequat e
clearance can reduce the refrigeration capacity of the
freezer and possibly cause permanent damage to the
compressor.
Water Connections
(Water Cooled Units Only)
An adequate cold water supply must be provided with
a hand shut--off valve. On the underside rear of the
base pan, two 3/8” I.P.S. water connections for inlet
and outlet have been provided for easy hook--up. 1/2”
inside diameter water lines should be connected to the
machine. (Flexible lines are recommended, if local
codes permit.) Depending on local water conditions, it
may be advisable to install a water strainer to prevent
foreign substances from clogging the automatic water
valve. There will be only one water “in” and one water
“out” connection. DO NOT install a hand shut--off valve
on the water “out” line! Water should always flow in this
order: first, through the automatic water valve; second,
through the condenser; and third, through the outlet
fitting to an opentrapdrain.
A back flow prevention device is required
on the incoming water connection side. Please
refer to the applicable National, State, and local codes
for determining the proper configuration.
Electrical Connections
In the United States, this equipment is intended to be
installed in accordance with the National Electrical
Code (NEC), ANSI/NFPA 70- 1987. The pur pose of the
NEC code is the practical safeguarding of persons and
property from hazards arising from the use of
electricity. This code contains provisions considered
necessary for safety. In all other areas of the world,
equipment should be installed in accordance with the
existing local codes. Please contact your local
authorities.
FOLLOW YOUR LOCAL ELECTRICAL CODES!
Each freezer requires one power supply. Check the
data label on the freezer for branch circuit overcurrent
protection or f use, c ircuit ampacity and electrical
specifications. Refer to the wiring diagram provided
inside of the control box for proper power connections.
CAUTION: THIS EQUIPMENT MUST BE
PROPERLY GROUNDED! FAILURE TO DO SO
CAN RESULT IN SEVERE PERSONAL INJURY
FROM ELECTRICAL SHOCK!
This unit is provided with an equipotential
grounding lug that is to be properly attached to the rear
of the frame by the authorized installer. The installation
location is marked by the equipotential bonding
symbol (5021 of IEC 60417-1) on both the removable
panel and the equipment’s frame.