Frymaster H14 Series Fryer User Manual


 
2–2
2.2 After Fryers Are Under The Fry Station Hood
Adjust casters so that fryers are level and at the proper height in the fry station hood. If necessary,
level the fryer(s) by loosening the locking screw on the caster leg and screwing the caster in or out.
When fryer is level and at proper height, retighten the locking screw on the caster leg.
Secure the fryer in place under the hood with the restraining hardware installed with the hood.
2.3 Power Requirements
DANGER
Copper wire suitable for at least 167°F (75°C) MUST
MUSTMUST
MUST be used for power connections.
MODEL VOLTAGE PHASE
WIRE
SERVICE
MIN.
SIZE
AWG
(mm
2
)
AMPS PER LEG
L1 L2 L3
H14 208 3 3 6 (16) 39 39 39
H14 240 3 3 6 (16) 34 34 34
H14 480 3 3 8 (10) 17 17 17
H14 220/380 3 4 6 (16) 21 21 21
H14 240/415 3 4 6 (16) 20 20 21
H14 230/400 3 4 6 (16) 21 21 21
ALL 208 3 3 6 (16) 39 39 39
14 SERIES 240 3 3 6 (16) 34 34 34
EPRI 220/380 3 4 6 (16) 21 21 21
UNITS 240/415 3 4 6 (16) 20 20 20
DANGER
The electrical power supply for this appliance MUST
MUSTMUST
MUST be the same as indicated on
the rating and serial number plate located on the inside of the fryer door.
DANGER
This appliance MUST
MUSTMUST
MUST be connected to the voltage and phase as specified on the
rating and serial-number plate located on the inside of the fryer door.
DANGER
All wiring connections for this appliance MUST
MUSTMUST
MUST be made in accordance with the
wiring diagrams furnished with the equipment. Wiring diagrams are located on the
inside of the fryer door.