Kraftware Corporation DS-16M2 Garbage Disposal User Manual


 
2
EMC Departmental Switches DS-16M2 and DS-32M2 Installation Guide
Device Power, Cooling, and Weight Information
Device Power, Cooling, and Weight Information
Device Dimensions
Device Placement Requirements
The DS-16M2 switches must be located at the top of the rack/cabinet,
because the power cord routing for these switches runs across the top
of the uppermost switch. There are no restrictions on the location of
the DS-32M2 switches in the rack/cabinet.
Power distribution must support the number of outlets required for
the switch and the switch power rating listed in the table on page 2.
Device Power Requirements
Cooling Requirements
(Heat Dissipation) Maximum Weight
DS-16M2 switch Voltage: 100 to 230 V ac, 47 to 63 Hz
5 amperes max
2 ac power cords per unit
410 BTU/hr 11.8 kg (26 lb)
DS-32M2 switch Voltage: 100 to 230 V ac, 47 to 63 Hz
5 amperes max
2 ac power cords per unit
836 BTU/hr 15.4 kg (34 lb)
Device Height Depth Width
DS-16M2 Switch 1.0 U 1.7 in 4.3 cm 25 in 63.5 cm 17.5 in 44.5 cm
DS-32M2 Switch 1.5 U 2.55 in 6.47 cm 25.1 in 63.75 cm 17.5 in 44.5 cm