York 28971AR Refrigerator User Manual


 
YORK INTERNATIONAL
FORM 201.18-EG1
11
TEMPERATURE AND FLOWS
(SI Units)
MODEL LEAVING WATER COOLER FLOW AIR ON
NUMBER
TEMPERATURE (°C) (L/S)
3
CONDENSER (°C)
YCAS MIN.
1
MAX.
2
MIN. MAX. MIN. MAX
0090EC 4.4 12.8 7.0 38.0 -17.7 51.7
0100EC 4.4 12.8 8.0 38.0 -17.7 51.7
0110EC 4.4 12.8 8.0 38.0 -17.7 51.7
0120EC 4.4 12.8 8.0 38.0 -17.7 51.7
0130EC 4.4 12.8 9.3 37.8 -17.7 51.7
0140EC 4.4 12.8 10.7 37.8 -17.7 51.7
0150EC 4.4 12.8 11.5 44.2 -17.7 51.7
0160EC 4.4 12.8 11.9 47.1 -17.7 51.7
0170EC 4.4 12.8 12.8 47.1 -17.7 51.7
0180EC 4.4 12.8 13.8 47.1 -17.7 51.7
0200EC 4.4 12.8 14.4 47.1 -17.7 51.7
0210EC 4.4 12.8 15.6 47.1 -17.7 51.7
0230EC 4.4 12.8 17.2 47.1 -17.7 51.7
0250EC 4.4 12.8 14.0 50.0 -17.7 51.7
0270EC 4.4 12.8 14.0 50.0 -17.7 51.7
0300EC 4.4 12.8 16.0 50.0 -17.7 51.7
0330EC 4.4 12.8 16.0 50.0 -17.7 51.7
0360EC 4.4 12.8 19.0 67.0 -17.7 51.7
0400EC 4.4 12.8 21.0 67.0 -17.7 51.7
0440EC 4.4 12.8 21.0 67.0 -17.7 51.7
NOTES:
1. For leaving brine temperature below 40°F (4.4°C), contact your nearest YORK office for application requirements.
2. For leaving water temperature higher than 55°F (12.8°C), contact the nearest YORK office for application guidelines.
3. The evaporator is protected against freezing to -20°F (-28.8°C) with an electric heater as standard.