York 28971AR Refrigerator User Manual


 
YORK INTERNATIONAL
84
Electrical Data (Continued)
OPTIONAL SINGLE-POINT POWER SUPPLY CONNECTION WITH INDIVIDUAL SYSTEM
CIRCUIT BREAKERS 3 & 4 COMPRESSOR UNITS (SEE FIG. 7)
(One Field Provided Power Supply Circuit to the chiller. Field connections to Power Terminal Block (standard) or Non-Fused Disconnect (option)
in Option Panel. Individual System Circuit Breakers in each Motor Control Center.)
See page 89 for Electrical Data footnotes.
FIELD SUPPLIED WIRING
CHILLER
FIELD PROVIDED POWER SUPPLY FACTORY PROVIDED (LUGS) WIRE RANGE
7
MODEL
YCAS
VOLTS
MCA
1
MIN NF OVER-CURRENT PROTECTION
13
TERMINAL BLOCK NF DISC. SWITCH
DISC SW
2, 9
MIN.
3, 5
MAX.
4, 6
(LUGS) WIRE RANGE (LUGS) WIRE RANGE
380 561 600 600 700 (2) 2/0-500 (2) 250-500
0250EC 460 464 600 500 500 (2) 1/0-300 (2) 250-500
575 372 400 400 450 (2) # 2-4/0 (3) 2/0-250
380 651 800 800 800 (2) 2/0-500 (3) 2/0-400
0270EC 460 534 600 600 700 (2) 2/0-500 (2) 250-500
575 427 600 500 500 (2) 1/0-300 (2) 250-500
380 678 800 800 800 (3) 1/0-300 (3) 2/0-400
0300EC 460 559 600 600 700 (2) 2/0-500 (2) 250-500
575 445 600 500 500 (2) 1/0-500 (2) 250-500
380 745 800 800 800 (3) 1/0-300 (3) 2/0-400
0330EC 460 612 800 700 700 (2) 2/0-500 (3) 2/0-400
575 487 600 600 600 (2) 1/0-300 (2) 250-500
380 835 1000 1000 1000 (3) 2/0-500 (4) 4/0-500
0360EC 460 689 800 800 800 (3) 1/0-300 (3) 2/0-400
575 550 600 600 600 (2) 2/0-500 (2) 250-500
380 896 1000 1000 1000 (3) 2/0-500 (4) 4/0-500
0400EC 460 739 1000 800 800 (3) 2/0-500 (4) 4/0-500
575 589 800 700 700 (2) 2/0-500 (3) 2/0-400
380 991 1200 1200 1200 (3) 2/0-500 (4) 4/0-500
0440EC 460 812 1000 1000 1000 (3) 2/0-500 (4) 4/0-500
575 647 800 800 800 (2) 2/0-500 (3 )2/0-400