Ratings SI Units
LCWT
AIR TEMPERATURE CONDENSER (°C)
(°C)
25 30 35 40 45 50
kWo kWE COP kWo kWE COP kWo kWE COP kWo kWE COP kWo kWE COP kWo kWE COP
5.0 1460.5 343.2 3.9 1372.3 383.9 3.3 1299.0 431.1 2.8 1227.2 483.4 2.4 1164.9 541.7 2.0 995.4 529.3 1.8
6.0 1505.0 348.4 4.0 1418.3 390.4 3.4 1338.6 438.0 2.8 1264.8 490.7 2.4 1201.9 550.7 2.1 1011.7 527.2 1.8
7.0 1550.0 353.5 4.0 1461.2 396.3 3.4 1379.8 444.8 2.9 1306.3 498.9 2.5 1239.8 559.5 2.1 1021.2 520.8 1.9
8.0 1595.5 358.6 4.1 1504.5 402.2 3.5 1419.3 451.2 2.9 1345.6 507.0 2.5 1278.1 568.5 2.1 1028.5 514.8 1.9
9.0 1641.4 363.7 4.1 1548.3 408.0 3.5 1463.0 458.4 3.0 1385.7 514.9 2.5 1314.2 575.7 2.2 1037.0 509.1 1.9
10.0 1687.8 368.6 4.2 1592.5 413.9 3.6 1505.3 465.2 3.0 1426.4 522.9 2.6 1339.7 575.2 2.2 1044.9 503.5 2.0
11.0 1734.6 373.6 4.3 1637.2 419.7 3.6 1548.1 472.1 3.1 1467.5 530.9 2.6 1363.5 575.2 2.2 1052.9 498.4 2.0
12.0 1781.9 378.5 4.3 1682.3 425.6 3.7 1591.3 479.1 3.1 1509.0 539.1 2.6 1388.8 575.5 2.3 1060.2 493.3 2.0
13.0 1829.6 383.5 4.4 1727.9 431.6 3.7 1634.8 486.1 3.2 1550.9 547.4 2.7 1413.6 575.8 2.3 1067.0 488.4 2.1
MODEL YCAS0400EC
NOTES:
1. kW = Compressor Input Power
2. EER = Chiller EER (includes power from compressors, fans, and control panels 0.8 KW)
3. LCWT = Leaving Chilled Water Temperature
4. Ratings based on 2.4 GPM cooler water per ton
5. Rated in accordance with ARI Standard 550/590.