40.0 389.6 508.6 8.6 383.6 547.0 7.9 375.6 579.4 7.4 355.8 588.5 6.9 312.8 549.3 6.5 246.4 470.6 5.9
42.0 401.7 514.3 8.8 396.4 554.4 8.1 385.1 582.3 7.5 361.6 584.3 7.0 317.8 546.4 6.6 248.4 465.7 6.0
44.0 414.1 520.1 9.0 408.6 560.8 8.3 394.8 585.3 7.7 367.4 580.3 7.2 320.6 539.0 6.7 250.4 461.0 6.1
45.0 420.4 522.9 9.1 414.6 564.0 8.3 400.3 586.7 7.8 370.4 578.2 7.3 322.0 535.2 6.8 251.5 458.3 6.1
46.0 427.0 525.7 9.2 420.9 567.2 8.4 405.1 588.1 7.8 373.3 576.2 7.4 323.4 531.5 6.9 252.5 455.8 6.2
48.0 439.7 531.4 9.4 431.9 570.0 8.6 415.5 591.1 8.0 379.3 572.1 7.5 325.8 523.8 7.0 254.5 450.9 6.3
50.0 453.0 537.1 9.5 443.0 572.5 8.8 426.1 594.0 8.2 385.5 567.8 7.7 328.6 516.5 7.2 256.6 446.0 6.4
52.0 466.5 542.9 9.7 454.4 575.1 9.0 436.1 595.3 8.3 391.6 563.8 7.9 331.3 509.3 7.3 258.6 441.1 6.6
55.0 487.3 551.9 10.0 471.8 579.1 9.3 448.1 590.7 8.6 399.9 557.3 8.1 335.5 498.7 7.6 261.3 433.5 6.7
MODEL YCAS0440EC
MODEL YCAS0400EC
40.0 352.0 455.7 8.7 341.2 485.6 7.9 331.4 517.3 7.2 321.9 550.8 6.6 293.5 538.0 6.2 243.5 480.3 5.7
42.0 364.4 463.6 8.8 353.1 494.1 8.0 343.1 526.6 7.4 333.4 560.9 6.7 300.8 539.4 6.3 246.0 475.1 5.8
44.0 376.9 472.0 9.0 365.3 502.6 8.2 355.2 536.0 7.5 343.1 565.5 6.9 307.9 541.2 6.4 248.4 469.9 5.9
45.0 383.0 475.9 9.0 371.9 507.3 8.3 360.8 540.3 7.6 346.9 565.2 7.0 311.6 542.2 6.5 249.6 467.4 6.0
46.0 389.6 480.1 9.1 378.1 512.0 8.3 366.7 544.9 7.6 350.9 565.1 7.0 315.2 543.1 6.6 250.7 465.0 6.0
48.0 402.5 488.3 9.3 390.6 520.8 8.5 379.6 555.3 7.7 358.8 566.3 7.2 322.2 544.5 6.7 252.9 460.5 6.2
50.0 415.5 496.6 9.4 403.5 529.8 8.6 392.2 565.3 7.9 366.6 566.8 7.3 325.1 536.8 6.9 254.9 456.1 6.3
52.0 428.7 505.0 9.6 416.4 539.0 8.7 404.2 573.6 8.0 374.4 567.6 7.5 328.0 530.4 7.0 257.0 452.0 6.4
55.0 448.9 517.7 9.8 436.1 553.0 8.9 419.8 580.2 8.2 385.9 568.9 7.7 331.8 520.4 7.2 259.8 446.2 6.5
LCWT
AIR TEMPERATURE ON CONDENSER (°F)
(°F)
100 105 110 115 120 125
TONS kW EER TONS kW EER TONS kW EER TONS kW EER TONS kW EER TONS kW EER
NOTES:
1. kW = Compressor Input Power
2. EER = Chiller EER (includes power from compressors, fans, and control panels 0.8 KW)
3. LCWT = Leaving Chilled Water Temperature
4. Ratings based on 2.4 GPM cooler water per ton
5. Rated in accordance with ARI Standard 550/590.