York 28971AR Refrigerator User Manual


 
YORK INTERNATIONAL
44
C
B
17 1/4"
C
B
1 11/16"
91 3/8"
88"
CONTROL CENTER
MICRO-COMPUTER
OPTIONS PANEL
CONNECTION)
1 15/16" (EDGE OF
UNIT TO COOLER
VIEW A-A
CONTROL
TRANSFORMER
SERVICE SWITCH
POWER: MULTIPLE POINT WITH TERMINAL BLOCKS
Dimensions YCAS0110 0120EC (English)
NOTES:
1. Placement on a level surface free of obstructions (including snow, for winter operation) or air recirculation ensures rated performance,
reliable operation and ease of maintenance. Site restrictions may compromise minimum clearances indicated below, resulting in unpre-
dictable air flow patterns and possible diminished performance. YORKs unit controls will optimize operation without nuisance high pres-
sure safety cutout; however, the system designer must consider potential performance degradation. Access to the unit control center
assumes the unit is no higher than on spring isolators. Recommended minimum clearances: Side to wall - 6'; rear to wall - 6'; control
panel end to wall - 4'; top - no obstructions allowed; distance between adjacent units - 10'. No more than one adjacent wall may be higher
than the unit.
LD04474
1"
9"
2"
1" TYP.
CONTROL ENTRY
(8) 7/8" DIA. HOLES
2 1/4"
5"
3 1/2"
17"
1" TYP.
CONTROL ENTRY
(7) 1/2" CONDUIT K.O.'S
3 SPA. @ 5"
1 3/4"
5"
3 1/4"
9"
17"
7"
POWER ENTRY
(8) 1 1/2",2",2 1/2" CONDUIT K.O.'S
2"
VIEW C-CVIEW B-B
LD04473