Teledyne 6712FR Refrigerator User Manual


 
6712FR Refrigerated Sampler
Section 5 Extended Programming
5-39
5.19.4 Dialout Alarms Dialout alarms require the sampler to be equipped with the
factory-installed 2400 baud talking modem, or the external
digital cellular CDMA or GSM modem. The dialout alarm allows
the sampler to notify a contact list when an “alarm” condition
exists (is true).
At the transition to the true state, any programmed I/O output
can cause the sampler to warn of the alarm condition. As many
as three telephone numbers can be entered. The sampler tries
each telephone number in succession until the alarm is acknowl-
edged. For each alarm condition, the sampler will attempt each
telephone number entered a maximum of five times, at user spec-
ified intervals.
Alarms are set up through the I/O programming menu, shown in
Section 5.19.3. “I/O1”, “I/O2”, and “I/O3” represent the three
alarms.
Example: Dialout Alarms
If the controller is equipped with a dialout modem, it
can be programmed to notify a telephone or pager
contact list when an alarm condition is true.
Before proceeding the I/O conditions must be defined.
Refer to section 5.19.4. These steps program a dialout
alarm when the condition defined for I/O1 is true.
1. Select YES to enable the dialout alarm.
The controller asks the same question for IO2 and
IO3. Select NO.
2. Using the number entry keys, enter as many as 3
telephone numbers to the contact list.
If the phone number requires extended characters,
or if you need to designate a number as a pager,
press the decimal key. The controller displays:
Use an arrow key to select a code and press Enter
to insert it in the number on the DIALOUT
NUMBERS screen.
3. Enter the delay time between each attempt. A
delay will allow time between attempts so you can
return a call to the controller to acknowledge the
alarm condition.
Note: Numbers may be removed from the list by
advancing the cursor to the very end of the number
with the right arrow key, then pressing the left arrow key
to erase the number.
DIALOUT WHEN IO1
BECOMES TRUE?
YES
NO
DIALOUT WHEN IO2
BECOMES TRUE?
YES
NO
DIALOUT WHEN IO3
BECOMES TRUE?
YES NO
DIALOUT NUMBERS:
1. 9,55555550001
2. 9,55555550002
3.
P
5550003
SELECT CODE
,#*
PAGER
__ MINUTE
DELAY BETWEEN CALLS
(0-99)