Carrier 30GN040-420 Refrigerator User Manual


 
Table 4A Capacity Control Steps, 040-070 (cont)
UNIT
30GN
CONTROL
STEPS
LOADING SEQUENCE A LOADING SEQUENCE B
%
Compressors
%
CompressorsDisplacement Displacement
(Approx) (Approx)
045 (50 Hz)
050 (60 Hz)
A1†**,B1**
1 18 A1†† 20 B1††
2 31 A1* 38 B1*
344A1 56B1
4 56 A1††,B1* 64 A1,B1††
5 73 A1††,B1 82 A1,B1*
6 87 A1*,B1 100 A1,B1
7 100 A1,B1
050 (50 Hz)
060 (60 Hz)
A1†,B1
1 28 A1*
242A1 — —
3 87 A1*,B1
4 100 A1,B1
050 (50 Hz)
060 (60 Hz)
A1†,B1**
1 28 A1* 38 B1*
242A1 58B1
3 67 A1*,B1* 67 A1*,B1*
4 87 A1*,B1 80 A1,B1*
5 100 A1,B1 100 A1,B1
050 (50 Hz)
060 (60 Hz)
A1†**,B1
1 15 A1††
2 28 A1*
3 73 A1††,B1
4 87 A1*,B1
5 100 A1,B1
050 (50 Hz)
060 (60 Hz)
A1†**,B1**
1 15 A1††
2 28 A1*
342A1 — —
4 53 A1,B1*
5 73 A1††,B1
6 87 A1*,B1
7 100 A1,B1
050 (50 Hz)
060 (60 Hz)
A1†,B1**
1 18 B1††
2 38 B1*
3— 58B1
4 60 A1,B1††
5 80 A1,B1*
6 100 A1,B1
050 (50 Hz)
060 (60 Hz)
A1†**,B1**
1 15 A1†† 18 B1††
2 28 A1* 38 B1*
342A1 58B1
4 53 A1††,B1* 60 A1,B1††
5 73 A1††,B1 80 A1,B1*
6 87 A1*,B1 100 A1,B1
7 100 A1,B1
060 (50 Hz)
070 (60 Hz)
A1†,B1
1 33 A1*
250A1 — —
3 83 A1*,B1
4 100 A1,B1
060 (50 Hz)
070 (60 Hz)
A1†,B1**
1 33 A1* 33 B1*
250A1 50B1
3 67 A1*,B1* 66 A1*,B1*
4 83 A1*,B1 83 A1,B1*
5 100 A1,B1 100 A1,B1
060 (50 Hz)
070 (60 Hz)
A1†**,B1
1 16 A1††
2 33 A1*
3 66 A1††,B1
4 83 A1*
5 100 A1,B1
060 (50 Hz)
070 (60 Hz)
A1†**,B1**
1 16 A1††
2 33 A1*
350A1 — —
4 66 A1††,B1
5 83 A1*,B1
6 100 A1,B1
060 (50 Hz)
070 (60 Hz)
A1†,B1**
1 16 B1††
2 33 B1*
3— 50B1
4 66 A1,B1††
5 83 A1,B1*
6 100 A1,B1
*Unloaded compressor.
†Compressor unloader, standard.
**Compressor unloader(s), accessory.
††Two unloaders, both unloaded.
7