5 - 16 PANELWARE MMI Application Manual for GE Fanuc Genius Protocol - June 1995 GFK-1115
5
Table 5 - 6. Possible Data Type Conversions for Series Five/Series Six
Panel Data PLC Data Types
Types
BIT WORD INT DWORD DINT FLOAT STRING
Bit
I, I1+,I2+, I1-,
O, O1+, O2+,
O1-, O2-, GI,
GQ
I, O, GI, GQ
(offset-1)%8=0
R, GAI, GAQ
(offset-1)%8=0
Byte u.
I, I1+,I2+, I1-,
O, O1+, O2+,
O1-, O2-, GI,
GQ
I, O, GI, GQ
R, GAI, GAQ
(offset-1)%8=0
R, GAI, GAQ
(offset-1)%8=0
Word u.
I, I1+,I2+, I1-,
O, O1+, O2+,
O1-, O2-, GI,
GQ
I, O, GI, GQ
R, GAI, GAQ
(offset-1)%8=0
R, GAI, GAQ
(offset-1)%8=0
R, GAI, GAQ
Word s.
R, GAI, GAQ
(offset-1)%8=0
R, GAI, GAQ
(offset-1)%8=0
R, GAI, GAQ
Long u.
R, GAI, GAQ R, GAI, GAQ
Long s.
R, GAI, GAQ R, GAI, GAQ
Float
R, GAI, GAQ
String
R, GAI, GAQ