If the calculated IAQ minimum position is greater than
the IAQ maximum damper position configuration then it
will be clamped to the configured value.
Demand
Limit
If the RTU--MP receives a level 1 (one degree offset), 2
(two degree offset), or a 3 (4 degree offset) to the BACnet
demand limit variable, the controller will expand the
heating and cooling setpoints by the configured demand
limit setpoint value and remain in effect until the BACnet
demand limit variable receives a 0 value.
FASTENER TORQUE VALUES
See Table 32 for torque values.
Table 32 – Torque Values
Supply fan motor mounting 120 +/ --- 12 in --- lb s
Supply fan motor adjustment plate 120 +/ --- 12 in --- lb s
Motor pulley setscrew 72+/--- 5 in---lbs
Fan pulley setscrew 72+/--- 5 in---lbs
Blower wheel hub setscrew 72+/--- 5 in---lbs
Bearing locking collar setscrew 65 --- 70 in --- lbs
Compressor mounting bolts 65 --- 75 in --- lb s
Condenser fan motor mounting bolts 20 +/ --- 2 in --- lbs
Condense r fan hub setscrew 84 +/ --- 12 in --- lb s