Mitsubishi Electronics FX5U Coffeemaker User Manual


 
136
APPENDIX
Appendix 3 I/O Module
Output specifications
There is the simultaneous ON ratio of available PLC inputs or outputs with respect to the ambient temperature.
For details, refer to Page 22 Input/Output Derating Curve
Relay output
Input circuit configuration • When using external power supply by input module
When using external power supply by powered input/output module
Item Specifications
No. of output points FX5-8EYR/ES 8 points
FX5-16EYR/ES 16 points
FX5-32ER/ES 16 points
Connection type Terminal block (M3 screws)
Output type Relay
External power supply 30 V DC or less
240 V AC or less
(250 V AC or less when the module does not comply with CE UL, cUL standards)
Output circuit insulation Mechanical insulation
Indication of output operation LED is lit when output is on
Max. load 2 A/point
The total load current of resistance loads per common terminal should be the following value.
4 output points/common terminal: 8 A or less
8 output points/common terminal: 8 A or less
Open circuit leakage current
Min. load 5 V DC, 2 mA (reference values)
Response time OFFON Approx. 10 ms
ONOFF Approx. 10 ms
Output circuit configuration
Item Specifications
Input module Input module
Source input wiring
0V
24V
S/S
X
S/S
Sink input wiring
CPU module
5.6 k
0V
24V
S/S
X
S/S
CPU module
5.6 k
24V
N
L
100 to 240 V AC
Fuse
X
S/S
0V
Source input wiring
24V
N
L
100 to 240 V AC
Fuse
X
S/S
0V
Sink input wiring
5.6 k 5.6 k
Powered input/output module Powered input/output module
Load
Fuse
Fuse
Y
COM0
Y
COM1
AC power
supply
DC power
supply