6 WIRING
6.6 Output Wiring
Transistor output
■Sink output type
*1 The output circuit of the PLC does not have a built-in fuse.
Provide a fuse suitable for each load to prevent melting of the wires on the circuit board caused by output device breakdown due to load
short-circuiting.
*2 "" represents vacant terminals.
Y0
COM0
Y7
Y0
COM1
Y7
Load
PL
Power ON
MC
MC
MC MC
DC power supply
Load
Fuse
*1
Fuse
*1
Load
Load
Fuse
*1
Fuse
*1
AC power supply (100 to 240 V)
Breaker
Y0
COM0
Y14
COM3
Y4
COM1
*2
Emergency
stop
Power supply for loads connected to
PLC output terminals
As for emergency stop operation, see "DESIGN
PRECAUTIONS" at "Safety Precautions" field.